CH1 circuit:
-
Heating curve no.: selection of a heating curve (see Chapter Heating curve).
Note, the parameter is present when the control is set according to heating curve [Configuration -> Heating -> Regulation
type: Acc. curve]
,
-
Curve offset: Heating curve offset (see section Curve heating).
Note that the parameter is present when the control is set according to heating curve [Configuration -> Heating -> Regulation
type: acc. curve]
.
-
MAN flow temperature system flow temperature when operating with constants parameters (manual setting of the heating
medium)
[Configuration -> Heating -> Regulation type: Fixed parameters]
,
-
Temp. MAX: maximum flow temperature of the heating circuit.
ATTENTION: setting too high temperatures, not suitable for building parameters, type of heating used and degree building
insulation can be carried out, among others, by to generate high operating costs.
- Circulation:
Yes - activation of the CH1 circuit,
No - turning off the circuit.
Nothe, the CH1 circuit is intended for heating connection radiator.
•
CH2 circuit:
-
Heating curve no.: selection of a heating curve (see Chapter Curve heating).
Note that the parameter is present when the control is set according to heating curve [Configuration -> Heating -> Regulation
type: acc. curve],
-
Curve offset: heating curve offset (see section Curve heating).
Attention, the parameter is present when the regulation is set according to the heating cuve [Configuration -> Heating ->
regulation type: Fixed parameters].
-
MAN flow temperature system flow temperature when operating with constants parameters (manual setting of the heating
medium)
[Configuration -> Heating -> Regulation type: Fixed parameters]
,
-
Temp. MAX: maximum flow temperature of the heating circuit.
ATTENTION: setting too high temperatures, not suitable for building parameters, type of heating used and degree building
insulation can be carried out, among others, by to generate high operating costs.
-
valve time: time needed to switch the valve by 90 degrees C. Adjustment range from 60 to 480 seconds, factory default 120
seconds. During configuration, please check the set value with the value of the valve drive used,
-
Dynamics of regulation: the response speed of the valve drive to achieve the corresponding parameter in the CH2 circuit. PL-
-102B ... Default valve - average, in case of too slow investigation temperature of the CH2 circulation medium to the set value,
should be increased dynamics. In the event of an overregulation of the medium temperature, dynamics should be reduced.
- circulation:
Yes - activation of the CH2 circuit,
No - turning off the circuit.
• Cooling:
- Type:
Off: cooling function inactive,
Fan coil,
Plane.
-
Temperature of the medium: temperature of the refigerant,
-
Hysteresis: Hysteresis for the refigerant.
• Cylinder:
-
Time without immersion heater: the parameter defines the time after which the heat pump is supported it will be an addi
-
tional source of heat (immersion heater) if it does not reach the set value water temperature in the tank. Time is counted
from the moment of reaching temperature of bivalent point [Configuration -> Heat pump -> Bivalent point]. In case the
outside temperature is above temperature of the bivalent point, the additional heat source will not remain included. If there
is a need for an additional heat, the condition for its activation is the activation of the immersion heaters
[Configuration ->
Heating element -> use of immersion heaters: Yes]
.
-
Frost protection:
Yes - activation of the storage tank frost protection in stand-by mode,
No - function inactive.
- Cylinder:
Yes - DHW tank circuit activation,
No - cylinder inactive.