OUTDOOR UNIT
HPMO2-8
HPMO2-12
HPMO2-16/23
Heating power A+2/W35
kW
7,1
11,3
20,5
Power consumption A+2/W35
kW
1,78
2,87
5,11
Efficiency factor A+2/W35
-
4,01
3,94
4,02
Heating power A+7/W35
kW
2,3 - 8,2
3,8 - 12,5
7,0 - 23,0
Power consumption A+7/W35
kW
0,5 - 1,84
0,8 - 2,95
1,47 - 5,9
Efficiency factor A+7/W35
-
4,6 - 4,46
4,75 - 4,24
4,76 - 3,89
Heating power A-7/W35
kW
5,8
9,2
17,1
Power consumption A-7/W35
kW
1,66
2,73
4,93
Efficiency factor A-7/W35
-
3,49
3,37
3,47
Cooling capacity A35/W7
kW
1.56 - 6.0
2,2 - 10,0
5,3 - 15,0
Power consumption A35/W7
kW
0.63 - 2.36
1,1 - 3,8
2,03 - 6,59
Efficiency factor EER A35/W7
-
2.48 - 2.54
2,0 - 2,63
2,61 - 2,28
Electrical installation
Electric supply
230V 1N AC, 50Hz
230V 1N AC, 50Hz
400V 3N AC, 50Hz
Degree of protection
IP X4
IP X4
IP X4
Maximum power consumption
kW
2,9
4,95
8,3
Maximum operating current
A
13
21,5
15
Power wire gauge*
mm
2
3x2,5
3x2,5
5x2,5
* Recommended power wire for outdoor unit
H07BQ-F 3x2.5mm
2
450/750V for outdoor use
H07BQ-F 3x2.5mm
2
450/750V for outdoor use
H07BQ-F 3x2.5mm
2
450/750V for outdoor use
Maximum outer diameter of ducting D 18mm
Heating system
Hydraulic connection
G1 (female thread)
G1 (female thread)
G1 (female thread)
Nominal flow
m
3
/h
1,0
1,7
2,9
Minimum flow
m
3
/h
0,6
0,7
0,85
Internal pressure drop
kPa
10
20
45
Maximum temperature of heating medium
°C
65
65
65
Air and noise
Maximum DC power of fan
W
85
170
2x75
Maximum air flow
m
3
/h
3000
4500
2x2500
Minimum/maximum air temperature
°C
-25/43
-25/43
-25/43
Maximum sound pressure level at 1m distance
dB(A)
52
55
56
Maximum sound power level
dB(A)
60
63
64
Refrigerant
Refrigerant type
R32
R32
R32
Compressor
Rotary with double piston Rotary with double piston Rotary with double piston