Minimum clearances for the indoor module
In combination with the R32 refrigerant: Absolutely observe the minimum
room area in addition to the minimum distances.
Mounting the indoor module on a wall
■
Maintain the minimum room size.
■
Provide adequate supply and exhaust ventilation systems.
■
Do not use any sources of ignition in the technical room, e.g. sources of open flame, a gas device being turned on, an electric
heater with exposed heating elements, etc.
Do not smoke in the technical room.
■
Electrical components installed at a distance of 1 m from those elements that conduct the refrigerant in the system must
comply with the requirements specified in relation to potentially explosive zones, Zone 2.