The heat pump:
-
Bivalent point: the limiting outdoor temperature up to which the heat pump operates autonomously. Below this point, an
additional heat source (heater) is activated,
- Shut-down temperature: the limit outdoor temperature at which the heat pump will shut down. If heating is required for
central heating or hot tap water, the heater will be the only heat source.
-
Max power: max power setting for HPM2.Z-16/23.
•
Room temperature:
-
TR control: room temperature control.
Yes - heating will be switched off once the set room temperature read by the room temperature sensor has been reached
No - room temperature control switched off. The room temperature reading does not affect the central heating operation.
-
TR hysteresis: room temperature hysteresis when Room Control is activated
-
TR calibration: calibrates the value of the indicated room temperature. The parameter is added or subtracted from the value
measured depending on the sign.
• Circulation:
Yes - DHW circulation pump control system enabled,
No - DHW circulation pump system turned off.
• Pumps:
-
Pumps protection: short-term activation time of the circulation pumps with a longer one standstill (blocking protection),
- Venting:
Off - venting turned off,
CH1 - CH1 circulation venting enabled,
CH2 - CH2 circulation venting enabled,
During the venting procedure (10min) the heat pump in the hydraulic module runs alternately at maximum and minimum
speed and the pumps the respective circuits are on. Thanks to this, concentration occurs air bubbles, which makes it easier
to remove them from the installation.
• Communication:
-
Device no.: device number on the communication system.
PARTY / HOLIDAY / MANUAL
Quickly switch the hot water algorithm as required.
• Party: setting the duration of the mode (from 1 to 24 hours or until cancelled).
• Holiday: setting the duration of the mode (from 1 to 60 days or until cancelled).
•
Manual: room temperature setting implemented by the control system: until cancelled.
* If any of the modes above is activated, it is possible to deactivate it after entering "Party / Holiday / Manual".
* The symbol of the activated mode is indicated on the main function screen.