9� Communication
87
© Copyright Reserved KONICS Co., Ltd.
Parameter
Addr
Description
Setting range
Unit
Default
CH1 In Bias
40313
CH 1 input correction
-999 to 999
Digit
000
CH1 Tag Name
40314
CH 1 channel
name
Front two characters,
E.g.) C H - 1
-
CH
40315
Rear two characters,
E.g.) C H - 1
-
-1
CH2 Record
※
3
40319
CH 2 using/recording
0: USE, 1: NO USE
-
On
CH2 In Type
※
3
40320
CH 2 input type
Same as addr. 40301
setting
-
TC.K1
CH2 Temp Unit
※
3
40321
CH 2 temp. unit
0:
℃,
1:
℉
-
℃
CH2 Lo Graph
※
3
40322
CH 2 graph low-limit
scale value
※
Refer to the 8.2.1
(4), (5)
Digit
-200
CH2 Hi Graph
※
3
40323
CH 2 graph high-limit
scale value
1350
CH2 Lo Range
※
3
40324
CH 2 low-limit input value
※
Refer to the 8.2.1
(6), (7)
-
-
CH2 Hi Range
※
3
40325
CH 2 high-limit input value
-
-
40326 -
-
-
-
CH2 Lo Scale
※
3
40327
CH2 low-limit scale
display value
-1999 to 9999
Digit
000.0
CH2 Hi Scale
※
3
40328
CH 2 high-limit scale
display value
100.0
CH1 Hi Scale
Decimal Point
※
2
40329
CH 1 scale dot position
0:0, 1:0.0, 2:0.00,
3:0.000
0.0
CH2 DP Unit
※
3
40330
CH 2 record display unit
Same as addr. 40311
-
%
CH2 In Bias
※
3
40331
CH 2 input correction
-999 to 999
Digit
000
CH2 Tag Name
※
3
40332
to
40333
CH 2 channel name
Same as addr. 40313
to 40314
-
CH-2
※
1: Displays only when input type(In Type) is temperature sensor.
※
2: Displays only when input type(In Type) is analog (voltage/current).
※
3: Displays only for 2 channels model.
(4) Record mode setup group [Record Setup]
Parameter
Addr
Description
Setting range
Unit
Default
Rec Mode
40080
Record mode
0: Graph 1: Digital
-
Graph
Rec Speed
※
1
40081
Record speed
0: 10, 1: 30, 2: 60, 3: 120,
4: 240 5: 480, 6: 960
mm/
hour
10mm
Memo Period
※
1
40082
Digital memo period
※
Refer to the 8.2.3 (6)
min
30min
Rec Period
※
2
40083
Record cycle
※
Refer to the 8.2.3 (9)
m.s
01m00s
Rec Font
40084
Record font
0: Korea, 1: English
-
Korea
Alarm Speed
40085
Record speed for alarm
0: 10, 1: 30, 2: 60, 3: 120,
4: 240, 5: 480, 6: 960
mm/
hour
10mm
※
1. Displays only when record mode (Rec Mode) is set as ‘Graph’.
※
2. Displays only when record mode (Rec Mode) is set as ‘Digital’.
Summary of Contents for KRN50 Series
Page 2: ... ii Copyright Reserved KONICS Co Ltd ...
Page 20: ...2 Specifications 20 Copyright Reserved KONICS Co Ltd ...
Page 22: ...3 Dimensions 22 Copyright Reserved KONICS Co Ltd ...
Page 24: ...4 Connections 24 Copyright Reserved KONICS Co Ltd ...
Page 28: ...6 Functions 28 Copyright Reserved KONICS Co Ltd ...
Page 34: ...7 General operation and parameter setting menu 34 Copyright Reserved KONICS Co Ltd ...
Page 66: ...8 Recording 66 Copyright Reserved KONICS Co Ltd ...
Page 71: ...8 Recording 71 Copyright Reserved KONICS Co Ltd ...
Page 75: ...8 Recording 75 Copyright Reserved KONICS Co Ltd ...
Page 77: ...8 Recording 77 Copyright Reserved KONICS Co Ltd ...