(8) Low-limit scale display value [CH Lo Scale]
In case of analog input type, this function is to set low-limit scale value
for assigned low-limit input value.
● Setting range: Within F.S. range (-1999 to 9999/-199.9 to 999.9/
-19.99 to 99.99/-1.999 to 9.999)
● Factory default: 0.0(unit: Digit)
(9) High-limit scale display value CH Hi Scale]
In case of analog input type, this function is to set high-limit scale value
for assigned high limit input value.
If assigned high/low-limit input value is 0V to 5V and user needs –100
to 100 value, user must set low-limit scale value: -100, high limit scale
value: 100. When input value is 0V, PV displays –100. If input value is
5V, PV displays 100.)
● Setting range: Within F.S. range (-1999 to 9999/-199.9 to 999.9/
-19.99 to 99.99/-1.999 to 9.999)
● Factory default: 100.0 (unit: Digit)
Display scale function is able to change display value for max./min.
measured input by setting high-limit scale [ Hi Scale ] and low-limit
scale [ Lo Scale ].
Summary of Contents for KRN50 Series
Page 2: ... ii Copyright Reserved KONICS Co Ltd ...
Page 20: ...2 Specifications 20 Copyright Reserved KONICS Co Ltd ...
Page 22: ...3 Dimensions 22 Copyright Reserved KONICS Co Ltd ...
Page 24: ...4 Connections 24 Copyright Reserved KONICS Co Ltd ...
Page 28: ...6 Functions 28 Copyright Reserved KONICS Co Ltd ...
Page 34: ...7 General operation and parameter setting menu 34 Copyright Reserved KONICS Co Ltd ...
Page 66: ...8 Recording 66 Copyright Reserved KONICS Co Ltd ...
Page 71: ...8 Recording 71 Copyright Reserved KONICS Co Ltd ...
Page 75: ...8 Recording 75 Copyright Reserved KONICS Co Ltd ...
Page 77: ...8 Recording 77 Copyright Reserved KONICS Co Ltd ...