4: Operation
30
TS_600_00 PW1000 1-3kVA User Manual 6/4/17
4.5.4 Operating parameters
setting menu
Figure 4.11 shows the operating
parameters than can be accessed
and adjusted by the user.
1. Ensure that the UPS output is
turned OFF.
2. To access the settings menu,
press the
ON
and
DOWN
buttons simultaneously for
three seconds, until the buzzer
beeps twice.
3. Press the
DOWN
button
repeatedly to scroll down to
the parameter the you wish to
change.
4. To change a parameter, press
the
UP
button to scroll through
the option range until the
required value is shown.
5. To select the chosen value
press the
DOWN
button.
a) This will temporarily store
the value and scroll down
to the next parameter
menu screen.
6. When you reach the final
screen (
Inverter Voltage
Adjust
), press the
ENTER
button.
a) Any changes are now
saved.
b) The LCD return to its
default screen
7. Turn
OFF
the UPS utility mains
supply and allow 1 minute for
the UPS electronics to fully
power down.
8. When the utility mains power
is next turned on, the UPS will
operate with the new
parameter settings applied.
CAUTION: These
parameters should be
adjusted by an
electrically-trained
engineer who is aware of
the effects on the system
of any changes made.
Buzzer
Testing
V
Inverter
Voltage
Hz
Bypass
Frequency Window
Mode
Bypass
Voltage
Window
Mode
Frequency
%
Inverter
Voltage Adjust
Enter
ON
Figure 4.11 Operating parameter setting menu
Hi
Lo
1
3
200
208
220
230
240
Std
Eco
3
2
1
0
50
60
3
2
1
0
(See paragraph 4.5.1)
(See paragraph 4.5.2)