Specification
Model Rating
1 kVA
2 kVA
3 kVA
Apparent output power
VA
1000
2000
3000
Real output power (@180-300VAC, PF=0.9)
W
900
1800
2700
Autonomy time (standard battery 100% load)
min.
>4
>4
>3
Topology
Double conversion on-line VFI-SS-111
Form factor
19"-Rack / Tower
Input:
Nominal voltage
VAC
Single phase, 110 - 300 VAC (@60% load)
Single phase, 150 - 300 VAC (@75% load)
Single phase, 180 - 300 VAC (@100% load)
Frequency
Hz
50 or 60 Hz, ± 5 Hz
Power factor
>0.99 at full rated linear load
Input power connection
10A IEC 320-C14
10A IEC 320-C14
16A IEC 320-C20
Output:
Voltage
VAC
Single phase, 230 VAC, selectable at 200/208/220/230/240 VAC
2 switched programmable outputs (setting via software)
Switching time Inverter-Bypass (typical)
ms
4ms (typical)
4ms (typical) / 0ms (optional)
Voltage regulation
%
±1 (until low battery warning)
Frequency
Hz
50/60 Hz, ±0.2% Unless synchronised to line
Synchronisation window
Hz
±3 Hz or ±1 Hz (selectable)
Voltage distortion (THD)
%
≤ 3% (linear load), ≤ 7% (non linear load)
Overload capability (AC Mode)
(Tolerance ±1%)
%
<105% Load = continuous operation,
from 106%...120% Load = transfer to bypass after 30 Sec.
from 121%...150% Load = transfer to bypass after 10 Sec
>150% Load = transfer to bypass immediately
Buzzer continuously alarms
Overload capability (BATTERY Mode)
(Tolerance ±1%)
%
Up to 105% Load = continuous operation,
from 106%...120% Load = shut down after 30 Sec.
from 121%...150% Load = shut down after 10 Sec
>150% Load = shut down immediately
Buzzer continuously alarms