background image

Site Preparation,

Installation and Operator’s Manual

for

Avaya

Avaya Series 1

Uninterruptible Power Systems

Model 3000 VA, 200–240V

Select Code 167-405-119

Comcode 407578822

Summary of Contents for 1 Series

Page 1: ...Site Preparation Installation and Operator s Manual for Avaya Avaya Series 1 Uninterruptible Power Systems Model 3000 VA 200 240V Select Code 167 405 119 Comcode 407578822 ...

Page 2: ...ction against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the us...

Page 3: ...ation Installation and Operator s Manual for Avaya Avaya Series 1 Uninterruptible Power Systems Model 3000 VA 200 240V Select Code 167 405 119 Comcode 407578822 Issue 6 Copyright 2001 Avaya Inc All Rights Reserved ...

Page 4: ...resent and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information BYPASS Indicates bypass control switches INPUT BREAKER Indicates the input breaker which shuts off utility power to the UPS electronics BATTERY BREAKER Indicates the battery breaker which shuts off battery power power transmission through the battery co...

Page 5: ...UPS WITH BDM QUICK INSTALLATION 1 Battery Module UPS Module Bypass Distribution Module BDM 60 Hz 2 Bypass Switch NORMAL Position 3 Battery Breaker I O ON OFF I O ON OFF I ON ...

Page 6: ...UPS with BDM Quick Installation 4 5 The UPS output voltage and the BDM input voltage is factory configured for 208V If you need to change the voltages see UPS with Bypass Module Startup on page 40 6 ...

Page 7: ...UPS with BIM Quick Installation UPS WITH BIM QUICK INSTALLATION 1 Bypass Isolation Module BIM 50 Hz Battery Module UPS Module 2 Bypass Switch NORMAL Position 3 Battery Breaker I O ON OFF I O ON OFF I ON ...

Page 8: ...UPS with BIM Quick Installation 4 5 The UPS output voltage is factory configured for 208V If you need to change the output voltage see UPS with Bypass Module Startup on page 40 6 ...

Page 9: ... Storage 27 Important Installation Notes Read Before Installing the UPS 27 Systems That Require Contact Closure 28 Systems That Require a Serial Interface 28 UPS with Bypass Module Installation 28 REPO Installation 38 UPS with Bypass Module Startup 40 Troubleshooting Tips 42 4 UPS Operation 43 UPS Front Panel 43 Operating Modes 44 Normal Mode 44 Bypass Mode 45 Battery Mode 45 Diagnostics 46 Batter...

Page 10: ...tions Menu 56 UPS Communications Interface Port 59 Communications Mode Reference Chart 61 6 Specifications 63 UPS Model 3000 Specifications 63 UPS Physical Specifications 63 Model 3000 Specifications with the 60 Hz BDM 64 Model 3000 Specifications with the 50 Hz BIM 64 UPS Technical Specifications 65 7 Troubleshooting 67 Resetting the UPS 69 Silencing the Alarm 69 Service and Support 69 Parts List...

Page 11: ...ilable power Voltage spikes power surges brownouts and power failures have the potential to corrupt critical data destroy unsaved work sessions and in some instances damage expensive hardware Now you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment The Bypass Distribution Module BDM and Bypass Isolation Module BIM have a Mainten...

Page 12: ...watts W amperes or amperes max A or volt amperes 2 If the rating is in watts multiply by 1 4 to obtain the VA requirement this is the typical relationship between watts and volt ampere ratings in most computing equipment However in some new computing equipment the power supply is power factor corrected and the watts rating equals the VA requirement Check with the manufacturer to determine applicab...

Page 13: ...sing or transmitting data when a power outage occurs Battery Times for the UPS and BIM During a power failure the UPS battery supplies power to your equipment providing time to complete computing activities prior to UPS shutdown The duration of this time period is directly related to the UPS battery configuration By adding battery modules you can customize the UPS to provide enough battery time fo...

Page 14: ...PS with BDM Load VA Load W Average Battery Time in Minutes Load VA Load W 1 Module 2 Modules 3 Modules 600 402 36 8 88 146 800 533 27 6 66 110 1200 800 18 4 44 73 1600 1067 13 7 33 54 2000 1333 10 7 26 42 2500 1667 8 3 20 33 3000 2000 6 5 16 27 NOTE If using an EBC refer to the EBC manual for approximate battery times ...

Page 15: ...es may carry live voltage even when the UPS is not connected to an AC supply S Never dispose of batteries in a fire Batteries may explode when exposed to flame S Never open or mutilate batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic S Use only the power supply cord provided with this UPS The power cord is wired in accordance with National Electrical Code N...

Page 16: ...s with hardwired outputs overcurrent protection for the output AC circuit s is to be provided by others S For Bypass systems with hardwired outputs suitably rated disconnect switches for the output AC circuit s are to be provided by others Sikkerhedsanvisninger VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE SIKKERHEDSANVISNINGER FARE Denne UPS indehol...

Page 17: ... en bør ikke betjenes nær vand eller høj fugtighed maksimalt 95 S Netledningen må ikke fjernes og stikket må ikke trækkes ud mens UPS en er tændt Dette fjerner sikkerhedsjorden fra UPS en og fra det udstyr der er sat til S I overensstemmelse med internationale normer og bestemmelser for el installation må det udstyr der er forbundet til udgangen af denne UPS tilsammen ikke overskride en jordafdeli...

Page 18: ...n kunnen ontploffen S Nooit batterijen openen of beschadigen Vrijkomend elektrolyt is schadelijk voor de huid en ogen en kan uiterst giftig zijn S Uitsluitend het elektriciteitssnoer gebruiken dat bij deze UPS wordt geleverd Het snoer is volgens de specificaties van de IEC International Electrical Code bedraad Controleer of wandcontactdoos waarop de UPS wordt aangesloten volgens deze zelfde specif...

Page 19: ...ding S Voor Bypass systemen met vast bedrade uitgangen moet de overstroombeveiliging voor wisselstroom uitgangcircuit s door derden worden geleverd S Voor Bypass Module systemen met vast bedrade uitgangen moeten de juiste hoofdschakelaars voor wisselstroom uitgangcircuit s door derden worden geleverd Tärkeitä turvaohjeita TÄRKEITÄ TURVAOHJEITA SUOMI SÄILYTÄ NÄMÄ OHJEET TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ ...

Page 20: ...äpuhtauksia Ympäristön lämpötila ei saa ylittää 40 C Älä käytä lähellä vettä ja vältä kosteita tiloja 95 maksimi S Älä poista tai irrota sisääntulojohtoa kun UPS on kytkettynä Tämä poistaa turvamaadoituksen UPS laitteesta ja siihen liitetystä laitteistosta S Kansainväliset normit ja johdotusmääräykset vaativat että kaikkien tämän UPS laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 2 7...

Page 21: ... Ne jamais ouvrir ou mutiler des batteries L électrolyte dégagé est nuisible à la peau et aux yeux et peut s avérer extrêmement toxique S Utiliser uniquement le cordon d alimentation fourni avec l onduleur Ce cordon est câblé conformément aux spécifications du Code électrique international CEI S assurer que le câblage de la prise secteur devant être utilisée avec l onduleur est lui aussi conforme ...

Page 22: ... de courant alternatif est à se procurer auprès d un autre fournisseur S Pour les systèmes de bypass dotés de sortie à bornier les interrupteurs adaptés au circuit de courant alternatif sont à se procurer auprès d un autre fournisseur Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN AUFBEWAHREN DIESES HANDBUCH ENTHÄLT WICHTIGE SICHERHEITSANWEISUNGEN WARNUNG Die USV führt lebensgefäh...

Page 23: ...der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit max 95 betreiben S Das Eingangskabel nicht entfernen oder abziehen während die USV eingeschaltet ist weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird S Um internationale Normen und Verdrahtungsvorschriften zu erfüllen dürfen die an den Ausgang dieser USV angeschlossenen Geräte zusammen ein...

Page 24: ... 167 405 119 Issue 6 Uncontrolled Copy S 0 1 2 3 4 5 36 6 7 60 S 8 69 4 2 2 7 2 8 69 S 8 8 0 8 6 8 8 8 2 S 6 7 6 2 S 7 2 9 9 9 3 63 8 6 0 6 0 S 48 7 8 48 2 7 8 7 9 2 2 48 ABCDEAF GFHIBJCIAF DKH G L 3 9 8 2 7 8 8 7 4 7 9 3 63 0 L 3 9 6 2 2 4 6 L 3 9 8 9 9 6 7 2 ...

Page 25: ...05 119 Issue 6 Uncontrolled Copy S 4 8 6 0 4 9 4 6 9 36 8 0 6 MNO 6 3 P QRS S 3 6 48 7 8 7 7 0 8 8 S 7 8 9 2 8 2 8 0 2 8 8 0 8 8 2 U VR W S 8 3 2 U 0 6 8 DEXDYY 8 4 6 6 8 68 6 6 8 3 6 48 8 S 4 8 0 8 3 6 G0 8 48 7 8 8 8 S 6 1 8 0 8 2 4 0 8 S 6 1 8 0 8 8 2 8 6 2 4 0 8 ...

Page 26: ... autonoma le batterie Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuità non è collegato con una fonte di alimentazione a corrente alternata S Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme S Mai aprire nè mutilare le batterie poichè l elettrolita da esse rilasciato è nocivo alla cute e agli occhi e può essere a...

Page 27: ...tinuità non deve avere una corrente di dispersione di terra superiore a 2 75 milliampere S La presa di alimentazione principale non deve trovarsi a oltre 2 metri dall apparecchiatura e deve essere accessibile all operatore L interruttore on off del gruppo statico di continuità non isola elettricamente i componenti interni Scollegare l unità dalla presa di alimentazione quando rimane in riposo per ...

Page 28: ...emmelser Sjekk at stikkontakten som anvendes for UPS en er koblet i overensstemmelsen med de samme spesifikasjonene for å unngå skade på utstyr Sjekk også at det finnes overstrømvern for vekselstrømkontakten under installeringen Sjekk at støpselet er ført helt inn i stikkontakten Bruk kun en en faset tre trådet jordet vekselstrømkontakt S For å redusere fare for brann eller elektriske støt bør den...

Page 29: ...istência técnica devem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO Não há nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS PERIGO S As baterias podem apresentar o risco de choque elétrico ou queimaduras provenientes de alta corrente de curto circuito Observe as instruções adequadas S Siga as instruções apropriadas ao desfazer se das baterias Consulte os códig...

Page 30: ...va máx 95 S Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada Isto removerá o aterramento de segurança da UPS e do equipamento conectado S Para estar de acordo com os padrões internacionais e os regulamentos de fiação o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 2 75 miliampères S O soquete de alimentação principal deve es...

Page 31: ...Данный ИБП содержит собственные источники энергии аккумуляторы На выходных розетках может иметься напряжение даже когда ИБП не подключен к сети переменного тока S Никогда не бросайте аккумуляторы в огонь Аккумуляторы могут взорваться под воздействием огня S Никогда не открывайте и не деформируйте аккумуляторы Вытекающий электролит опасен для кожи и глаз и может быть крайне токсичным S Пользуйтесь ...

Page 32: ...ая величина тока утечки на землю всего оборудования подключенного к выходу ИБП не должна превышать 2 75 миллиампера S Настенная розетка должна находиться в пределах 2 метров от оборудования и быть доступной для оператора Выключатель ИБП не отключает внутренние узлы от входного электропитания При отключении оборудования на продолжительные интервалы времени отсоедините входной сетевой шнур от настен...

Page 33: ...de corriente alterna c a S Nunca deseche las baterías en el fuego Las baterías pueden explotar si se las expone a la llama S Nunca abra ni dañe las baterías El electrolito que se libera es perjudicial para la piel y los ojos y puede ser extremadamente tóxico S Utilice solamente el cable de entrada que se suministra con este SIE El cable está instalado según las especificaciones del NEC Código Eléc...

Page 34: ...ida del SIE tienen corriente eléctrica siempre que se oprime el botón pulsador de conexión de salida del SIE Output ON aun cuando el cable de entrada esté desconectado S Para los sistemas de bypass con salidas cableadas la protección por sobreintensidad para el los circuito s de la salida de c a se deberá adquirir a un tercero S Para los sistemas de bypass con salidas cableadas los interruptores d...

Page 35: ...peratur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer Omgivande temperatur får ej överstiga 40 C Använd inte utrustningen nära vatten eller vid hög luftfuktighet max 95 S Ta aldrig bort nätsladden när UPS enheten är påslagen Detta tar bort säkerhetsjordningen från både UPS enheten och den anslutna utrustningen S För att överensstämma med internationell standard oc...

Page 36: ...Safety Warnings 26 Avaya Model 3000 UPS Operator s Manual S 167 405 119 Issue 6 Uncontrolled Copy ...

Page 37: ...ot exceed 35 C 95 F in order to preserve battery life For longer term storage energize the UPS and battery module for approximately 8 hours every 90 days in order to maintain battery charge Whenever the units are not energized verify the circuit breaker on all battery modules is returned to the OFF O position see Figure 5 on page 32 Important Installation Notes Read Before Installing the UPS UPS a...

Page 38: ...400 configuration provides alarms which are normally open when the alarm is not present and closed when an alarm occurs 2 Connect the alarm adapter to the unit s RS 232 port and the modular output to the computer wallfield etc through an 8 pin modular plug Comcode PEC For 3B2 systems use 406707737 24024 For all other systems use 407691401 24433 Systems That Require a Serial Interface 1 For install...

Page 39: ...y for seismic applications but can also be used to prevent rolling or tipping of the assembled rack A F F F Fo o o or r r r S S S Se e e ei ii is s s sm m m mi ii ic c c c I I I In n n ns s s st t t ta a a al ll ll ll la a a at t t ti ii io o o on n n n Prepare the floor by referring to the hole pattern shown below The mounting plate has four 0 375 diameter floor mounting holes for earthquake bolt...

Page 40: ...ing four of the 1 4 20 x 1 2 screws provided See Figure 3 or Figure 4 for part locations Battery Module Bypass Distribution Module BDM 60 Hz UPS Module Stacking Module Cover the smaller flanges without holes face toward the front 1 4 20 x 1 2 Screws 1 4 20 x 1 2 Screws Caster Base Floor Mounting Plate Figure 3 UPS with Distribution Module Setup ...

Page 41: ...attery Module Caster Base Floor Mounting Plate 1 4 20 x 1 2 Screws Figure 4 UPS with Isolation Module Setup 3 Stack the modules onto the caster base according to the stacking order shown in Figure 3 or Figure 4 The first module should nest on the base and each additional module nests on the preceding one If multiple Stacking Modules are used the caster bases may be secured together on the side wit...

Page 42: ...dule rear panel is in the NORMAL position see Figure 5 or Figure 6 BDM 60 Hz 427 79 mm 16 84I 251 6 mm 9 91I Depth of Unit 400 0 mm 15 75I Power Output Receptacles Utility Input Connector UPS Module Breaker Tie Circuit Breaker Battery Module External Battery Connector Battery Cord Bypass Switch Load Circuit Protectors Input Circuit Protector Battery Connector Power Output Receptacle Power Input Co...

Page 43: ... Module Battery Connector Power Input Connector Serial Port External Battery Connector Battery Cord BIM 50 Hz Y Cord Utility Input Connector Output Breaker Power Output Receptacles Bypass Switch 427 79 mm 16 84I 251 6 mm 9 91I Depth of Unit 400 0 mm 15 75I Input Breaker Input Circuit Protector Power Output Receptacle Tie Wrap Mounts Figure 6 UPS with BIM Rear Panel ...

Page 44: ...ker on all battery modules or EBCs 10 Switch the circuit breaker on all battery modules to the ON position 11 Two tie wraps are included with the UPS to secure the Y cord to the input and output receptacles on the UPS rear panel Insert the tie wrap through the slot on each tie wrap mount 12 Plug the Y cord of the Bypass Module into the power connectors on the UPS rear panel as shown in Figure 5 or...

Page 45: ...age 38 18 Start the UPS according to the UPS with Bypass Module Startup procedure on page 40 19 Refer to your national and local electrical codes for acceptable external wiring practices WARNING Only qualified service personnel such as a licensed electrician should perform the hardwired installation 20 Remove the three screws on the terminal block access cover with a Phillips screwdriver and remov...

Page 46: ...he terminal access box see Figure 7 and hardwire to the terminal block See Figure 8 and Figure 9 for the 60 Hz hardwired BDM wiring or Figure 10 for the 50 Hz hardwired BIM wiring See note Ground Neutral 120V 88V 120V 240V To customer provided distribution panel NOTE 208 Vac single phase is available between L2 5 and L1 4 However the voltage available between N 6 and L1 4 is only 88 Vac NOT 120 Va...

Page 47: ... 119 Issue 6 Uncontrolled Copy Ground Line 1 Line 2 Neutral Ground Neutral Line 2 Line 1 120V 240V Input Output Figure 9 60 Hz Hardwired BDM Terminal Block Ground Line Neutral Ground Neutral Line 220 230 240V Input Output Figure 10 50 Hz Hardwired BIM Terminal Block ...

Page 48: ...5 mm2 75 C copper wire minimum 23 Replace the terminal box cover 24 If you are using a REPO switch follow the instructions in the following section REPO Installation 25 Start the UPS according to the UPS with Bypass Module Startup procedure on page 40 REPO Installation WARNING Only qualified service personnel such as a licensed electrician should perform the hardwired installation The REPO switch ...

Page 49: ...see the following table Tighten the compression terminals with a screwdriver 2 Pivot the REPO receptacle guard out of the way plug the REPO plug receptacle UPS connector into the REPO receptacle on the UPS rear panel and twist the connector in place see Figure 5 on page 32 or Figure 6 on page 33 Mounting Holes Plug Receptacle UPS Connector Three Foot Cord Terminal Block Access Hole for Conduit Fig...

Page 50: ...Hz BDM 208 240 120 Set to 220V for 110V BDM output Set to 230V for 115V BDM output Set to 208V or 240V for 120V BDM output 50 Hz BIM 208 Model 2500 only 208 50 Hz BIM 220 220 50 Hz BIM 230 230 50 Hz BIM 240 240 The UPS output voltage must match input voltage 3 If your Bypass Module is a hardwired unit supply utility power You have 30 seconds after supplying power to press the Output Off button Rel...

Page 51: ...ottom Each time you press the button the UPS beeps and the next two indicators flash NOTE If you do not save a selection within two minutes the setup automatically aborts and switches back to the original configuration 7 Press and hold the Output On button until the alarm beeps to select and save the output voltage Failure to release the button immediately after the beep will cause the UPS to abor...

Page 52: ...ator remains lit and the Output On indicator turns on The front panel displays the percentage of full load being applied to the UPS The UPS is now in Normal mode with the load online See Normal Mode on page 44 for more information Troubleshooting Tips If you should encounter any problems during startup see the troubleshooting chart on page 67 The battery modules are shipped with the batteries char...

Page 53: ...S Displays the loading percentage during Normal mode and the battery capacity during Battery mode You can also use the front panel to configure UPS communication options and to configure the UPS output voltage See Front Panel Communications Access on page 54 or Changing the Output Voltage on page 47 OUTPUT OFF OUTPUT ON ALARM SILENCE Overload Indicator Unlit Amber Green Flashing Indicator Legend I...

Page 54: ...tifier Battery Circuit Breaker Battery Module Optional Battery Module Optional Battery Module EBC Battery Charger Input Plug EMI RFI Filter Input Circuit Breaker Inverter Bypass Load Relay UPS Load AC Input to BDM BDM UPS Load Figure 16 UPS Block Diagram Normal Mode During Normal mode the µindicator illuminates and the front panel displays the percentage of UPS load capacity being used by the prot...

Page 55: ...nd then once every 10 seconds while in Battery mode The indicator illuminates The front panel displays the approximate percentage of battery capacity remaining see Figure 19 When the utility power returns the UPS switches to Normal mode operation while the battery recharges BATTERY ONLINE 75 CAPACITY REMAINS BATTERY ONLINE 50 CAPACITY REMAINS BATTERY ONLINE 25 CAPACITY REMAINS BATTERY ONLINE BATTE...

Page 56: ...ture Test The UPS also runs a series of over 20 internal tests when power is first applied If a diagnostic test fails see Chapter 7 Troubleshooting on page 67 Battery Test on Demand You can perform a battery test on the UPS while it is operating in Normal mode by pressing the Output On button The UPS automatically distributes some of the load to the batteries for 30 seconds and tests the battery s...

Page 57: ...UPS shutdown 1 Press and hold the Output Off button until the long beep ceases approximately three seconds The µindicator remains lit indicating Normal mode load offline 2 Unplug the UPS The UPS enters Battery mode for several seconds The µindicator turns off and the UPS shuts down 3 When all LEDs are no longer illuminated on the UPS switch the circuit breaker to the OFF O position on each battery...

Page 58: ...ion and remove the UPS 1 Turn the Bypass switch on the Bypass Module to the BYPASS position see Figure 20 The Bypass Module is now powering your equipment from utility power 2 Press and hold the Output Off button until the long beep ceases approximately three seconds The µindicator remains lit 3 Remove the cord connections to the back of the UPS The UPS enters Battery mode for several seconds The ...

Page 59: ...r s Manual S 167 405 119 Issue 6 Uncontrolled Copy BDM 60 Hz UPS Module Circuit Breaker Battery Module Bypass Switch Battery Connector Power Output Receptacle Power Input Connector Y Cord Figure 20 UPS with Bypass Module Rear Panel 60 Hz BDM Shown ...

Page 60: ...o select the correct output voltage according to your Bypass Module Bypass Module Model Number UPS Voltage Selection 60 Hz BDM 208 120 208 208 60 Hz BDM 208 240 120 240 Set to 220V for 110 220V BDM output Set to 230V for 115 230V BDM output Set to 208V or 240V for 120 240V BDM output 60 Hz BDM 208 240 120 Set to 220V for 110V BDM output Set to 230V for 115V BDM output Set to 208V or 240V for 120V ...

Page 61: ...on within two minutes the setup automatically aborts and switches back to the original configuration 7 Press and hold the Output On button until the alarm beeps to select and save the output voltage Failure to release the button immediately after the beep will cause the UPS to abort the setup 8 Continue to Step 10 9 Plug the Y cord of the Bypass Module into the power connectors on the UPS as shown...

Page 62: ...UPS Operation 52 Avaya Model 3000 UPS Operator s Manual S 167 405 119 Issue 6 Uncontrolled Copy ...

Page 63: ... Mode Printer Mode 2400 Baud with Novell Contacts Printer Mode 19200 Baud with Novell Contacts S LAN Configuration Novell Style Network Interface 3Com Style Network Interface AS 400 Style Network Interface default Custom User Configurable Interface Initial Communications Settings The UPS is factory configured for AS 400 style LAN contacts To verify the initial UPS communications configuration you ...

Page 64: ... ll le e e e L L L LA A A AN N N N C C C Co o o on n n nt t t ta a a ac c c ct t t ts s s s Any baud rate other than 2400 or 19200 with Printer mode or not Printer mode A A A AS S S S 4 4 4 40 0 0 00 0 0 0 S S S St t t ty y y yl ll le e e e L L L LA A A AN N N N C C C Co o o on n n nt t t ta a a ac c c ct t t ts s s s N N N No o o o S S S Se e e er r r ri ii ia a a al ll l Default Select this mode...

Page 65: ...ime until the alarm beeps again A single indicator corresponding with the current setting remains flashing 4 Press the Output Off button to scroll through the communication options top to bottom Each time you press the button the UPS beeps and the next indicator flashes NOTE If you do not save a selection within two minutes the setup automatically aborts and switches back to the original configura...

Page 66: ...our terminal or operating system documentation for details on configuring your terminal communication settings 3 At the terminal prompt press Control C until the UPS Serial Communications Menu appears UPS SERIAL COMMUNICATIONS MENU SELECT OPERATION MODE ENTER SELECTION 1 CONTINUOUS DUMP 2 3 A B P L Z Q S POLLED DUMP SMART DUMP ASCII TERMINAL VT100 TERMINAL PRINTER DUMP LAN CONFIGURATION SET BAUD R...

Page 67: ...puter overhead when using this mode 2 Polled Dump Status information is transmitted only when requested by a poll character Control E 3 Smart Dump Status information is transmitted when polled as in the previous mode However the transmission also occurs automatically whenever UPS status changes For example if there is a power outage UPS status information changes and is therefore automatically tra...

Page 68: ...tes for configuring LAN communications A Inverter shutdown control is enabled active HIGH 12V SELECT CUSTOM LAN CONFIGURATION ENTER SELECTION B C Q TO QUIT THIS MENU Inverter shutdown control is enabled active LOW 12V Inverter shutdown control is disabled Instructions Choose the desired inverter shutdown function Warning It is recommended that this feature should not be used with normal RS 232 com...

Page 69: ...guration must correspond to the communications equipment you are using In particular new baud rate selections for the UPS must match your communications equipment UPS Communications Interface Port In addition to configuring the UPS for specific communication options you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment CAUTION The serial...

Page 70: ... the UPS serial port The connector body and style may vary as well NOTE Standard pin for pin cables may not work correctly Consult your network software or server manuals for system shutdown pin assignments The UPS serial port complies with EIA RS 232 standards RS 232 specifies a maximum cable length of 50 feet 15m See Figure 23 for the location of the serial port UPS Rear Panel Serial Port Detail...

Page 71: ...a from UPS RS232 RxD 3 N A Signal Ground 7 Novell Battery On ON AC 14 16 Open Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 Novell Battery On ON AC 14 16 Closed Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 3Com Shutdown Remote SHUT DOWN 2 Positive Voltage Low Battery LOW BATT 9 Positive Voltage Battery On PWR FAIL 10 Positive Voltage Signal Ground 7 AS 400 A D f l UPS Available ...

Page 72: ...Communication 62 Avaya Model 3000 UPS Operator s Manual S 167 405 119 Issue 6 Uncontrolled Copy ...

Page 73: ...00 2100 13 00A 14 42A 1081 1574 220 3000 2100 12 30A 13 64A 1006 1574 230 3000 2100 11 70A 13 04A 968 1574 240 3000 2100 11 30A 12 50A 923 1574 UPS Physical Specifications Parameter UPS Module Battery Module Bypass Module Height 252 mm 9 91 in 252 mm 9 91 in 252 mm 9 91 in Width 142 5 mm 5 61 in 142 5 mm 5 61 in 142 5 mm 5 61 in Depth 400 mm 15 75 in 400 mm 15 75 in 400 mm 15 75 in Weight 7 4 kg 1...

Page 74: ... 208 13 0A 14 4A 12 5A 12 5A 240 120 240 11 3A 12 5A 12 5A 12 5A 208 120 13 0A 25 0A 12 5A 12 5A 240 120 11 3A 25 0A 12 5A 12 5A 208 120 208 13 0A 12 5A 12 5A 14 4A 208 120 240 13 0A 12 5A 12 5A 12 5A 240 120 240 11 3A 12 5A 12 5A 12 5A 240 120 240 11 3A 12 5A 12 5A 12 5A Model 3000 Specifications with the 50 Hz BIM Voltage In Out Input Current Output Current Total not to exceed 2100 Watts 3000 VA...

Page 75: ...00 kHz Input Cord Detachable 2 meter cord with L6 30P Outlets UPS Module IEC 320 1 Output Voltages and Outlets with BDM 120 208V L6 30R or L14 30R 4x5 15R 120 240V L6 30R or L14 30R 4x5 15R 120 L5 30R 4x5 15R 208V Hardwired 120 208V 240V Hardwired 120 240V Output Voltages and Outlets with BIM 208V available with Model 2500 only 220 230 240V 1 x IEC 320 C19 3 x IEC 320 C13 220 230 240V Hardwired 22...

Page 76: ...Specifications 66 Avaya Model 3000 UPS Operator s Manual S 167 405 119 Issue 6 Uncontrolled Copy ...

Page 77: ...et breaker Load does not turn on UPS has not been activated Press the Output On button for one second then release UPS beeps occasionally Normal operation None UPS is protecting your equipment UPS input breaker trips Load fault Check the load Disconnect faulty load equipment Wait several minutes before resetting the UPS input breaker Restart the load indicator remains lit even though line voltage ...

Page 78: ...ator remains lit reset the UPS by pressing the Output On button until the alarm beeps You may need to obtain a larger capacity UPS OVERLOAD I1 I2 I3 OUTPUT ON The utility line voltage and frequency are out of specification The inverter remains online deriving power from the utility until it is no longer acceptable Check the unit configuration Refer to the product specifications see page 63 OVERLOA...

Page 79: ...t press the Output On button until the UPS alarm beeps Silencing the Alarm To silence the alarm for an existing fault press and hold the Output On button for one second The alarm becomes quiet If UPS status changes the alarm beeps overriding previous alarm silencing Press the Output On button again to silence the alarm Service and Support The troubleshooting chart on page 67 covers most of the dif...

Page 80: ...rdwired BDM 17 407464049 50 Hz BIM 220 230 240V PDM01 407465889 Cord connected EPDM L14 30P with 4 5 15R2 s PDM02 407465913 Cord connected EPDM L14 30P with 2 5 15R2 s and 2 L14 30R s PDM03 407483361 Cord connected EPDM L14 30P with 2 5 15R2 s 1 L6 30R and 1 L6 20R PDM04 407465905 Cord connected EPDM L14 30P with a hardwired output 2 pole 20A circuit breaker PDM05 407483353 Cord connected EPDM L5 ...

Page 81: ...y configuration 2 extension time 3 installation 28 storage 27 Battery Fault alarm 68 Battery Mode 45 Battery Start 46 Battery Test on Demand 46 baud rates 56 59 Bypass Distribution Module BDM AC Line operation 48 changing BDM input voltage 41 installation 28 Maintenance Bypass feature 28 operation 48 power output receptacles 32 rear panel hardwired 35 plug receptacle 32 startup 40 utility input co...

Page 82: ...on Menu 58 customer service 69 D Data Dump Modes 57 diagnostics 46 Display Configuration Screen 57 E exiting Main Menu 59 F front panel configuring communications 54 controls 43 display functions 43 indicators 43 front panel configuration 3Com 54 AS 400 54 Novell 54 printer mode 54 H hardwired Bypass Module rear panel 35 termination blocks 37 I indicators front panel 43 input cord 40 42 65 Input O...

Page 83: ...ftware 54 58 N Normal Mode operation 44 Novell Network Interface front panel configuration 54 LAN Configuration Menu 58 O On Battery or Bypass Indicator 43 Operating Modes 44 Operation Battery 45 Bypass 45 Normal 44 UPS with Bypass Module 48 Output Off Button 43 Output On Button 43 Output On Indicator 43 output voltage changing 47 initial setting 40 Overload condition 68 Indicator 43 Overtemperatu...

Page 84: ...sts 46 storage temperature 27 Switch BDM Input Voltage Selector Switch 32 Bypass 32 33 system requirements 2 T Terminal Modes 57 Tests Battery on demand 46 Startup 46 transistors contact ratings 59 troubleshooting chart 67 tips 42 U uninterruptible power system 1 UPS alarm silencing 69 alarms 68 block diagram 44 changing output voltage 47 communication 53 Communications Mode Reference Chart 61 fro...

Page 85: ......

Page 86: ...164201341 A 164201341A ...