![Kohler PW 9000DPA User Manual Download Page 23](http://html1.mh-extra.com/html/kohler/pw-9000dpa/pw-9000dpa_user-manual_1990180023.webp)
UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
3-5
3: Installation
These illustrations show that the UPS cabinet requires the following power cables:
Rectifier (In):
• three-phase (1L1, 1L2, 1L3)
• neutral (1N)
• protective earth (PE) connection for the rectifier input
Bypass (In):
• three-phase (2L1, 2L2, 2L3)
• neutral (2N)
• protective earth (PE) connection for the bypass if used as ‘Dual Feed’ input
Load (Out):
• three-phase (3L1, 3L2, 3L3)
• neutral (3N)
• protective earth (PE) connection for the load output
(External) Battery:
• Plus (+)
• Common (N)
• Minus (-)
• protective earth (PE) connection for the external batteries
Input neutral grounding
Figure 3.2 Input neutral grounding
Key Point:
Input neutral is required to operate the rectifier.
In TN-S systems, no 4-pole input switches or circuit breakers should be used.
During battery operation the neutral must always be grounded.
0V
230V
UPS
Summary of Contents for PW 9000DPA
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Page 2: ......
Page 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Page 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...