![Kohler PW 9000DPA User Manual Download Page 14](http://html1.mh-extra.com/html/kohler/pw-9000dpa/pw-9000dpa_user-manual_1990180014.webp)
2: Description
2-4
UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
2.3.5 PowerWAVE 9000DPA MX Frames
Figure 2.3 PowerWAVE 9000DPA MX Frames
2.4
Advanced Design Features
2.4.1 Hot-swappable
modules
In a redundant module system
(see paragraph 2.4.4)
the unique
Hot-Swappable
feature enables a UPS
module to be inserted or removed from the larger cabinet assembly whilst it is still powered (
hot
) without
affecting the supply to the load, and without having to transfer to bypass.
Note:
In a non-redundant configuration the load will unavoidable have to be transferred to bypass while a
module is removed from the system.
2.4.2 Advanced booster technology
The UPS module’s inbuilt advanced booster technology results in a perfect sinusoidal input power quality at
0.99 input power factor with a harmonic content of less than 3% THD(i). This leads to a more reliable total
system operation and savings in generator and transformer sizing as winding losses are minimised. It also
means that traditional harmonic filters are no longer required.
PowerWAVE DPA
MX Frames
CLASSIC
DPA-50
TRIPLE
DPA-150
UPGRADE
DPA-250
Capacity
Max.
1 module (30-45kVA)
280 x 7/9Ah batteries
3 modules (30-45kVA)
240x 7/9Ah batteries
5 modules (30-45kVA)
External batteries
Max. Power connection
kVA
50
150
250
Dimensions (WxHxD)
mm
730x1650x800 730x1975x800 730x1975x800
Weight of Empty Frame
kg
250
270
190
Weight of Frame with modules and
no batteries
kg
300 - 310
(with 1 Module)
420 - 450
(with 3 Modules)
440 - 490
(with 5 Modules)
Colours
Front: RAL 9007 + black (inlets). Sidewalls: Graffito grey
PowerWAVE DPA
MODULES
DPA 30
DPA 40
DPA 50
Output Apparent Power
KVA
30
40
45*
Output Active Power
KW
24
32
40
Output Power (PF=1)
KVA / KW
24 / 24
32 / 32
40 /40
Number of 12V Battery Blocks
No.
40-50
40-50
40-50
Dimensions (WxHxD)
mm
663 x 225 x 720
Weight UPS Module
kg
50
57
60
Colours
Front: RAL 9007
* On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW
Summary of Contents for PW 9000DPA
Page 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Page 2: ......
Page 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Page 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Page 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...