TP-6255 7/06
74
Section 8 Component Testing and Adjustment
8.11 Fault Shutdown Tests
Verify the operation of the generator set overspeed,
overcrank, and low oil pressure shutdowns by
performing the following tests.
If these tests are
inconclusive,
test
individual
shutdown
circuit
components (wiring harness, switch, etc.) as described
elsewhere in this section.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Moving rotor.
WARNING
Servicing the generator set when it is operating. Exposed
moving parts can cause severe injury or death.
Keep
hands, feet, hair, clothing, and test leads away from the belts
and pulleys when the generator set is running.
Replace
guards, screens, and covers before operating the generator
set.
Short circuits.
Hazardous voltage/current can cause
severe injury or death.
Short circuits can cause bodily injury
and/or equipment damage
.
Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
8.11.1 Controller Fault Shutdown
Functions
Check the operation of the fault functions programmed
in the ADC 2100 by performing the following tests. If the
ADC 2100 does not operate as described, check the
ADC configuration settings; see Section 7.5.2. Also
check the ADC 2100 wiring and connections; see
Section 10.
Overspeed Shutdown
The overspeed setting is programmed into the ADC
controller and is not adjustable. Verify that the following
controller configuration parameters are set correctly for
your unit. See Section 7.5.2 for the settings.
D
System voltage/frequency parameter (UU)
D
Unit configuration parameter (UC)
D
Engine type parameter (EC)
D
Engine data input type parameter (ED)
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
WARNING
Servicing the exhaust system.
Hot parts can cause
severe injury or death.
Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
Open the generator set output circuit breaker before
beginning the test.
(See Figure 8-16 for the circuit
breaker location.)
Connect a DVM to measure the output frequency. Start
the generator set and manually adjust the engine speed.
See Section 4.4.
Increase the engine speed to at least 115% of the rated
engine speed, 69 Hz on 60 Hz models or 58 Hz on 50 Hz
models. Verify that the generator set shuts down on an
overspeed fault (OS). If the overspeed shutdown does
not operate, the generator set should shut down on an
overfrequency fault (OF) after approximately 5 seconds.
Low Oil Pressure (LOP) Shutdown
Connect a jumper wire from the LOP switch (lead 13) to
the generator set ground. Start the generator set. Verify
that the generator set shuts down after approximately
25--35 seconds of operation. Remove the jumper wire
from the LOP switch and ground. Start the generator set
and run it for at least 25--35 seconds to verify that the
generator set does not shut down.
Overcrank Shutdown
Disconnect the starter motor lead at the starter solenoid
(K20) terminal. Move the controller master switch to the
RUN position. Observe that the generator set simulates
cranking for 15 seconds and then rests for 15 seconds.
Check that the generator set shuts down after the third
crank/rest cycle.
High Engine Temperature Shutdown
Connect a jumper wire across coolant temperature
sensor (CTS) connections P1-8 and P1-9. Start the
generator set. Verify that the generator set shuts down
approximately 5 seconds after the generator set comes
up to speed.
Remove the jumper wire.
Start the
generator set and run it for at least 30 seconds to verify
that the generator set does not shut down.
Summary of Contents for 6.5-27EFOZD
Page 1: ...Marine Generator Sets Models 8 32EOZD 6 5 27EFOZD TP 6255 7 06a Service ...
Page 12: ...TP 6255 7 06 12 Service Assistance Notes ...
Page 22: ...TP 6255 7 06 22 Section 1 Specifications Notes ...
Page 28: ...TP 6255 7 06 28 Section 3 Intake and Exhaust System Notes ...
Page 62: ...TP 6255 7 06 62 Section 7 Controller Notes ...
Page 78: ...TP 6255 7 06 78 Section 8 Component Testing and Adjustment Notes ...
Page 92: ...TP 6255 7 06 92 Section 10 Wiring Diagrams Notes ...
Page 100: ...TP 6255 7 06 100 ...
Page 101: ...TP 6255 7 06 101 ...
Page 102: ...TP 6255 7 06 102 ...
Page 103: ...TP 6255 7 06 103 ...