TP-6255 7/06
41
Section 6 Troubleshooting
Troubleshooting Chart, continued
Problem
Possible Cause
Corrective Action
Reference
Generator set
k b
No fuel
Check the fuel supply.
—
cranks but
does not start
Loose connection or open circuit
Check for loose or open
connections at the fuel solenoid
(lead 70A). Check the
controller/engine wiring continuity.
Section 10
Air cleaner clogged
Clean or replace.
Section 3
Incorrect controller configuration
Check for correct controller
configuration parameters: unit
configuration (UC) and engine
configuration (EC).
Section 7.5
No engine rotation sensed (check
for an overcrank fault shutdown)
Check for a locked rotor.
Section 8.6
Generator set
starts hard
Low battery voltage
Check battery voltage, power
supply, and operation.
Generator Set O/M
Air cleaner clogged
Replace element.
Section 3
Worn piston rings, valves
Check compression.
Engine S/M
Generator set
starts but
shuts down
Fault shutdown
Check for a fault shutdown code
on the Advance Digital Control’s
LED display. Correct the fault and
then move the generator set
master switch to the OFF/RESET
position to reset the ADC.
Section 7.4
Generator set
stops
suddenly
Fault shutdown
Check for a fault shutdown code
on the Advanced Digital Control’s
LED display. Correct the fault and
then move the generator set
master switch to the OFF/RESET
position to reset the ADC.
Section 7.4
No fuel
Check the fuel supply.
—
Fuel line restriction
Inspect fuel lines.
—
Air cleaner clogged
Replace element.
Section 3
Blown controller fuse (F3)
Replace fuse.
Section 8.12
Blown auxiliary winding fuse (F1)
Replace fuse. If fuse blows again,
test generator components.
Section 8.12
Blown relay interface board (RIB)
fuse (F2)
Replace fuse.
Section 8.12
Engine overheated (hot engine
only)
Check air intake, oil level, air
inlet/outlet.
Sections 2 and 3
Low oil pressure (LOP) shutdown
Attempt startup. If the unit shuts
down, remove the lead from the
LOP switch and reset the
controller. A successful restart
attempt indicates a faulty LOP
shutdown switch.
Note:
Check the engine oil
pressure before performing the
test and/or replacing the LOP
shutdown switch.
Section 8.11
Engine overloaded
Reduce electrical load.
Generator Set I/M
Loss of generator output voltage
to controller
Check connections at P15 plug.
Check continuity of AC sensing
leads 11 and 44 (for 1-phase
models) or leads 7, 8, and 9 (for
3-phase models).
Section 10
Faulty K3 (flash) relay
Check for Flash LED illumination.
Check RIB fuse. Replace relay
board.
Section 7.10
Summary of Contents for 6.5-27EFOZD
Page 1: ...Marine Generator Sets Models 8 32EOZD 6 5 27EFOZD TP 6255 7 06a Service ...
Page 12: ...TP 6255 7 06 12 Service Assistance Notes ...
Page 22: ...TP 6255 7 06 22 Section 1 Specifications Notes ...
Page 28: ...TP 6255 7 06 28 Section 3 Intake and Exhaust System Notes ...
Page 62: ...TP 6255 7 06 62 Section 7 Controller Notes ...
Page 78: ...TP 6255 7 06 78 Section 8 Component Testing and Adjustment Notes ...
Page 92: ...TP 6255 7 06 92 Section 10 Wiring Diagrams Notes ...
Page 100: ...TP 6255 7 06 100 ...
Page 101: ...TP 6255 7 06 101 ...
Page 102: ...TP 6255 7 06 102 ...
Page 103: ...TP 6255 7 06 103 ...