TP-6727 10/11
31
Section 3 Installation Instructions
Figure 3-7
Manual Fuel Shut-Off Valve (outdoor
installation shown)
3. Connect the fuel supply.
a. Apply pipe sealant that is approved for fuel
connections to the threaded fuel connections.
b. Use a section of flexible fuel line to connect the
fuel supply to the fuel inlet connection on the
generator set. See Figure 3-8 and Figure 3-9
for the fuel inlet connection location.
c. Open the manual fuel valves and leak test all
fuel connections using soapy water. If a leak is
detected, close the fuel valves, disconnect the
lines at the location of the leak, clean the
fittings,
and
apply
fresh
pipe
sealant.
Reconnect the lines and recheck for leaks.
Note:
After the system installation is complete,
check for fuel leaks with the generator
set running. See Section 3.8, Operation
Tests.
4. Check that the fuel system is set up for the fuel
being used (natural gas or LP). See Section 3.7.1.
1
1. Fuel supply connection, 3/4 NPT
2. Fuel solenoid valve
Note:
UL 2200-listed units include a second fuel valve. See
Figure 3-9.
2
ADV-7692
Figure 3-8
Fuel Supply Connection Location
(Generator set enclosure not shown)
2
GM39123
1. Fuel solenoid valves (qty. 2)
2. Fuel supply connection, 3/4 NPT
1
Figure 3-9
Fuel Supply Connection with Two Fuel
Valves
Summary of Contents for 15REYG
Page 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...
Page 16: ...TP 6727 10 11 16 Section 1 General Notes...
Page 44: ...TP 6727 10 11 44 Section 5 Controller Notes...
Page 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...
Page 64: ...TP 6727 10 11 64 Notes...
Page 65: ...TP 6727 10 11 65 Notes...
Page 66: ...TP 6727 10 11 66 Notes...
Page 67: ......