TP-6727 10/11
38
Section 5 Controller
then step through the following parameters. Use the up
(
∧
) and down (
∨
) arrow buttons to select the appropriate
setting for the application.
Note:
Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.
Voltage/frequency setting (Uu).
Select the system
voltage and frequency from the table in Figure 5-1.
Note:
This parameter sets the nominal system voltage
and frequency. To adjust the output (measured)
voltage, see Section 5.1.
Unit configuration (Uc).
This parameter sets the
generator set type. Select Uc01, standby.
Engine configuration (Ec).
The engine configuration
must match the generator set engine type.
Advanced configuration mode (Adnc).
The data
input types, battery voltage, and communications
setting can be changed in the advanced configuration
mode.
Press the up arrow button when
Adnc
is
displayed to enter the advanced configuration mode.
Engine data input types (Ed).
This setting defines the
type of senders used on the generator set engine.
Battery voltage (Bt).
This setting toggles between 12
and 24 VDC for the engine starting battery voltage.
Communications setting (Cn).
This setting allows the
user to set the controller for communication with
optional meters. The factory setting is Cn00, no CAN
communications. Change this setting if necessary. See
Figure 5-1.
CANbus address (CA).
This parameter sets the
CANbus address for the controller. The CA parameter
appears only on models with engines equipped with
ECMs.
Parameter
Setting
Description
Voltage, VAC
Frequency, Hz
Phases, Wires
Connection
Unit’s system voltage
and frequency
Uu01
120/240
60
Single phase, 3 wire
1 phase
Uu04
277/480
60
Three phase, 4 wire
Wye
Uu10
120/240
60
Three phase, 4 wire
Delta
Uu10
139/240
60
Three phase, 4 wire
Wye
Uu11
120/208
60
Three phase, 4 wire
Wye
Uu16
127/220
60
Three phase, 4 wire
Wye
Unit configuration
Uc01
Standby
Engine type
Ec11 *
30REYG
Ec12 *
15REYG
Engine data input types
Ed01
15/30REYG factory setup
Battery voltage
Bt12
12 VDC
Communications
Cn00
No CAN communications, 48-hour power down (factory setting)
Cn01
J1939 communications, no power down
Cn06
Enables J1939 communications and 1-hour ADC power down after engine stop
for either:
a. Remote start/stop switch
b. Automatic transfer switch
CANbus address
CA01
15/30REYG
* ADC application program version 3.25 or higher is required
Figure 5-1
Configuration Parameters
Summary of Contents for 15REYG
Page 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...
Page 16: ...TP 6727 10 11 16 Section 1 General Notes...
Page 44: ...TP 6727 10 11 44 Section 5 Controller Notes...
Page 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...
Page 64: ...TP 6727 10 11 64 Notes...
Page 65: ...TP 6727 10 11 65 Notes...
Page 66: ...TP 6727 10 11 66 Notes...
Page 67: ......