TP-6727 10/11
42
Section 5 Controller
TP6196
Move the generator set master switch to the RUN position. The generator set
engine starts and the controller display shows the engine runtime hours.
Display :*
or
To raise or lower the voltage in large increments
(approximately 5--7 volts per step).
To enter fine voltage adjustment mode.
To raise or lower the voltage in smaller increments
(approximately 0.5--0.7 volts per step).
or
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller “password.”)
x x
x x x x
1 P
1 P
* Shaded boxes show which character in the controller display changes for each adjustment.
X
in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model.
x.
The controller is now in the voltage coarse adjustment mode.
Press:
1 P
Continued on Figure 5-7.
x x
x x
x
x
Output Voltage Adjustment Mode:
Figure 5-6
Output Voltage Adjustments