TP-6727 10/11
39
Section 5 Controller
Wait about 5 seconds until the display shows the
firmware version number. (The number may be
different than the one shown here.)
Hold the Select button:
or
To set the voltage/frequency setting. See
Figure 5-1.
To step to the next parameter, unit configuration
Uc.
or
To set the unit configuration setting to Uc01, if
necessary.
To step to the next parameter, engine type Ec.
To step to the next parameter, advanced
configuration mode or save mode selection.
Move the generator set master switch to the RUN
position. (The generator set engine will not start.)
Display:
or
To set the engine type to Ec03 OR Ec06, if
necessary. See Figure 5-1.
U u
X X
U c 0 1
U u 0 1
3 2 5
.
0
A d n c
Press:
Now release the Select button.
or
To enter advanced configuration mode.
Go to Figure 5-3.
or
To proceed to the save mode without
entering the advanced configuration mode.
Go to Figure 5-4.
Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.
Press:
S A V E
E d 0 1
E c 0
X
Note:
Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed.
Press the down arrow key and then the up arrow
key 3 times to enter the configuration mode.
(This is the controller “password.”)
Controller Configuration Mode:
Figure 5-2
Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)
Summary of Contents for 15REYG
Page 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...
Page 16: ...TP 6727 10 11 16 Section 1 General Notes...
Page 44: ...TP 6727 10 11 44 Section 5 Controller Notes...
Page 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...
Page 64: ...TP 6727 10 11 64 Notes...
Page 65: ...TP 6727 10 11 65 Notes...
Page 66: ...TP 6727 10 11 66 Notes...
Page 67: ......