TP-6727 10/11
25
Section 3 Installation Instructions
Section 3 Installation Instructions
3.1 Introduction
Have the generator set installed by a trained, authorized
Kohler distributor, dealer, or authorized representative.
Note:
These instructions outline one procedure for
installing the generator set. Local codes may
require
different
procedures.
Install
the
equipment in compliance with the National
Electrical Code (NEC) and local codes.
Enclosed units must be installed outside. The exhaust
systems on enclosed units are designed for outdoor
installations.
Review the information in Section 1,
General, before beginning the installation procedure.
Note:
Do not install enclosed units inside a building.
Note: Outdoor Installations:
Install carbon monoxide
(CO) detector(s) on each level of any building
adjacent to a generator set. Locate the detectors
to adequately warn the building’s occupants of
the presence of carbon monoxide.
Open units may be installed inside a building.
The
exhaust must be piped safely outside, and adequate air
for combustion and cooling must be provided. Review
the information in Sections 1 and 2 before beginning the
installation procedure. See Figure 2-1 for a typical
open-unit installation.
Note: Indoor Installations:
For the protection of
generator set service technicians and any other
people that may enter the building, install carbon
monoxide (CO) detector(s) on each level of the
building.
Locate the detectors to adequately
warn the building’s occupants of the presence of
carbon monoxide.
Read and follow the safety precautions in this manual
and observe the decals on the equipment. Refer to the
diagrams and drawings in Section 7 for dimensions and
electrical connections during the installation procedure.
Read the entire installation procedure and obtain the
accessories and tools needed before beginning
installation. Perform the steps in the order shown.
To install optional accessories, follow the instructions
provided with each kit.
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection
of
standby
and
normal sources of supply.
WARNING
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death.
Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.
Electrically ground the
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment.
Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk
of electrocution.
Carbon monoxide.
Can
cause
severe
nausea,
fainting, or death.
The
exhaust
system
must
be
leakproof and routinely inspected.
WARNING
Carbon monoxide detectors.
Carbon monoxide can
cause severe nausea, fainting, or death.
Install carbon
monoxide detectors on each level of the building. Locate the
detectors to adequately warn the building’s occupants of the
presence of carbon monoxide.
Keep the detectors
operational at all times. Periodically test and replace the
carbon monoxide detectors according to the manufacturer’s
instructions.
Summary of Contents for 15REYG
Page 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...
Page 16: ...TP 6727 10 11 16 Section 1 General Notes...
Page 44: ...TP 6727 10 11 44 Section 5 Controller Notes...
Page 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...
Page 64: ...TP 6727 10 11 64 Notes...
Page 65: ...TP 6727 10 11 65 Notes...
Page 66: ...TP 6727 10 11 66 Notes...
Page 67: ......