Appendix D Gas Fuel System Installation Planning
Determining Propane Cylinder
Quantity
Guide for Installing 100 lb. Cylinders
For continuous draws where temperatures may reach
--18
°
C (--0
°
F). Assume the vaporization rate of 100 lb.
cylinder as approximately 50000 Btu/hr.
Number of cylinders/side = Total load in Btu
50000
Example:
Assume total load = 200,000 Btu/hour.
Cylinders/side = 200000= 4 cylinders/side
50000
The chart in Figure 1 shows the vaporization rate of
containers in terms of the temperature of the liquid and
the wet surface area of the container.
When the
temperature is lower or if the container contains less
liquid, the vaporization rate of the container is a lower
value.
Lb. of
Propane
in Cyl.
Maximum Continuous Draw In Btu/Hour At
Various Temperatures In
°
C (
°
F)
--18
°
C
(0
°
F)
--7
°
C
(20
°
F)
4
°
C
(40
°
F)
16
°
C
(60
°
F)
21
°
C
(70
°
F)
100
113000
167000
214000
277000
300000
90
104000
152000
200000
247000
277000
80
94000
137000
180000
214000
236000
70
83000
122000
160000
199000
214000
60
75000
109000
140000
176000
192000
50
64000
94000
125000
154000
167000
40
55000
79000
105000
131000
141000
30
45000
66000
85000
107000
118000
20
36000
51000
68000
83000
92000
10
28000
38000
49000
60000
66000
Figure 1
Vaporization Rate, 100 lb. Propane
Cylinders, Approximate
Determining Propane Vaporization
Capacity
Guide for ASME LP Gas Storage
Containers
% of
Container
Filled
K
Equals
Propane* Vaporization
Capacity at --18
°
C (0
°
F) in
Btu/Hr.
[
60
100
D x L x 100
50
90
D x L x 90
40
80
D x L x 80
30
70
D x L x 70
20
60
D x L x 60
10
45
D x L x 45
* These formulae allow for the temperature of the liquid to
refrigerate to --29
°
C (--20
°
F), producing a temperature
differential of --7
°
C (20
°
F) for the transfer of heat from the air to
the container’s
wetted
surface and then into the liquid. The
vapor space area of the vessel is not considered since its
effect is negligible.
[
D=outside diameter in inches
L=overall length in inches
K=constant for percent volume of liquid in container.
Figure 2
Propane Vaporization Capacity
Vaporizing Capacities for Other Air
Temperatures
Multiply the results obtained with the formulae in
Figure 2 by one of the factors in the following table for
the prevailing air temperature.
Prevailing Air
Temperature
Multiplier
--26
°
C
(--15
°
F)
0.25
--23
°
C
(--10
°
F)
0.50
--21
°
C
(--5
°
F)
0.75
--18
°
C
(0
°
F)
1.00
--15
°
C
(5
°
F)
1.25
--12
°
C
(10
°
F)
1.50
--26
°
C
(15
°
F)
1.75
--7
°
C
(20
°
F)
2.00
Figure 3
Propane Vaporization Temperature
Summary of Contents for 15REYG
Page 1: ...Commercial Generator Sets Models 15REYG 30REYG TP 6727 10 11c Installation...
Page 16: ...TP 6727 10 11 16 Section 1 General Notes...
Page 44: ...TP 6727 10 11 44 Section 5 Controller Notes...
Page 48: ...TP 6727 10 11 48 Section 6 Generator Reconnection Notes...
Page 64: ...TP 6727 10 11 64 Notes...
Page 65: ...TP 6727 10 11 65 Notes...
Page 66: ...TP 6727 10 11 66 Notes...
Page 67: ......