Section 7 Generator Troubleshooting
7.12 Stator
The stator produces electrical output (AC) as the
magnetized main field rotates within the stator windings.
The stator consists of a series of coils of wire laid in a
laminated steel frame. The stator leads supply voltage
to the AC load and exciter regulator.
Leads 1, 2, 3, and 4 are the generator set output leads.
Leads 55 and 66 are the voltage regulator supply and
sensing leads. The output of leads B1 and B2 is rectified
by BR1 to supply the control voltage. BR1 is located on
the controller circuit board.
Before testing the stator, inspect it for heat discoloration
and visible damage to the housing lead wires and
exposed and varnished areas of the frame laminations.
Be sure the stator is securely fastened in the stator
housing.
Test the condition of the stator according to the following
procedure. See Figure 7-20.
Stator Test Procedure:
1. Place the generator set start/stop switch in the
STOP position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Check the generator output lead connections. See
the installation manual for voltage reconnection
and Section 10 of this manual for the wiring
diagram.
4. Disconnect all the stator leads to isolate the
windings. To check the stator continuity, set the
ohmmeter on the R x 1 scale. Check the stator
continuity by connecting the meter leads to the
stator leads as shown in Figure 7-20 through
Figure 7-22. Perform the stator tests on all the
stator windings.
F+
F--
AC
AC
AC
TP-553615
F1
F2
33
3
55
44
4
1
2
B1
B2
1
2
3
4
5
6
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-20
Stator Ohmmeter Connections
Between Leads
Continuity
1 and 2
3 and 4
55 and 66
B1 and B2
1 and 3, 4, 33, 44
1 and 55, B1, and B2
4 and B1 and B2
55 and B1 and B2
Any stator lead and ground
Yes
Yes
Yes
Yes
No
No
No
No
No
Figure 7-21
Stator Continuity, 4-Lead
Between leads
Continuity
1 and 4
2 and 5
3 and 6
7 and 10
8 and 11
9 and 12
55 and 66
B1 and B2
1 and 2, 5, 3, 6, 7, 10, 8, 11, 9, 12
1 and 55, 66, B1, and B2
Any stator lead and ground
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Figure 7-22
Stator Continuity, 12-Lead
Summary of Contents for 10EOR
Page 10: ...10 Safety Precautions and Instructions TP 6073 4 06 Notes...
Page 12: ...TP 6073 4 06 12 Service Assistance Notes...
Page 22: ...TP 6073 4 06 22 Section 3 Intake and Exhaust System Notes...
Page 26: ...TP 6073 4 06 26 Section 4 Fuel System Notes...
Page 30: ...TP 6073 4 06 30 Section 5 Cooling System Notes...
Page 38: ...TP 6073 4 06 38 Section 6 Controller Troubleshooting Notes...
Page 54: ...TP 6073 4 06 54 Section 8 Component Troubleshooting Notes...
Page 60: ...TP 6073 4 06 60 Section 9 Generator Disassembly Reassembly Notes...
Page 82: ...TP 6073 4 06 82...
Page 83: ...TP 6073 4 06 83...