TP-6073 4/06
72
Section 10 Wiring Diagrams
10.12Four-Lead Reconnection
The following drawing illustrates the reconnection of
four-lead generator sets.
In all cases, follow the
National Electrical Code (NEC) guidelines.
NOTICE
Voltage reconnection.
Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
from an authorized service distributor/dealer.
100-120 Volt Configurations
GRD.
L1
L2
4
3
2
1
L0 (Neutral)
L0
Ground
Load
Side
Line
Side
Two-Pole
Circuit
Breaker
Jumper
lead
Figure 10-1
100-120 Volt, 3-Wire Configuration
If the installation requires a factory two-pole circuit
breaker, do not connect the load-side terminals of the
circuit breaker together; see Figure 10-1.
If the
installation requires a 100-120 volt, 2-wire system, use a
single-pole circuit breaker.
See Figure 10-2.
When
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on
the
line
side of the circuit breaker to balance the load of
the generator set.
4
3
2
1
Stator Leads
L0
GRD.
L1
L0 (Neutral)
Line
Side
Single-Pole
Circuit
Breaker
Ground
Load
Side
60 Hz
50 Hz
L0-L1
100-120 Volt
100-120 Volt
L0-L2
100-120 Volt
100-120 Volt
Figure 10-2
100-120 Volt 2-Wire Configuration
100-120/200-240 Volt Configurations
The 100-120/200-240 volt configuration does not use a
jumper lead. If the unit was originally wired for straight
100-120 volt, 3 wire, remove the jumper lead (see
Figure 10-1 for location).
Select a two-pole circuit
breaker. Application of two single-pole circuit breakers
does not conform to NEC requirements for supplying a
200-240 volt
load—even
if
the
breakers
are
mechanically attached together. Leads L1 and L2 are
for different phases—
never
connect them together.
Summary of Contents for 10EOR
Page 10: ...10 Safety Precautions and Instructions TP 6073 4 06 Notes...
Page 12: ...TP 6073 4 06 12 Service Assistance Notes...
Page 22: ...TP 6073 4 06 22 Section 3 Intake and Exhaust System Notes...
Page 26: ...TP 6073 4 06 26 Section 4 Fuel System Notes...
Page 30: ...TP 6073 4 06 30 Section 5 Cooling System Notes...
Page 38: ...TP 6073 4 06 38 Section 6 Controller Troubleshooting Notes...
Page 54: ...TP 6073 4 06 54 Section 8 Component Troubleshooting Notes...
Page 60: ...TP 6073 4 06 60 Section 9 Generator Disassembly Reassembly Notes...
Page 82: ...TP 6073 4 06 82...
Page 83: ...TP 6073 4 06 83...