Section 6 Controller Troubleshooting
6.2 Controller Circuit Board
It is possible to check some controller circuit board
components (relays) without removing them from the
board. Check these relays before installing a new board
and attempting startup. Use a high quality multimeter
and follow the manufacturer’s instructions. To obtain
accurate readings when testing, remove all the circuit
board connectors and conformal coating (transparent
insulation) from the component terminals. Use the chart
in Figure 6-2
The controller circuit board has LEDs to indicate the
presence of relay coil power and aid in circuit board and
generator fault detection. See Figure 6-1. When the
K1-K5 relays energize, the corresponding LEDs light.
The LEDs do not indicate whether the relay coil is
functional or not. This conclusion can only be reached
through analyzing the fault.
H-239563
1
4
5
6
7
8
9
10
12
13
2
3
11
1. Engine crank control relay (K3)
2. P1 connector
3. P2 connector
4. Time delay relay (K5)
5. LED5
6. LED2
7. Engine run relay (K2)
8. AC crank disconnect relay (K1)
9. LED1
10. Fault shutdown relay (K4)
11. Relay schematic
12. LED4
13. LED3
Figure 6-1
Controller Circuit Board H-239563
Component
Ohmmeter Connections
Procedure
Results
K1 Relay Coil
K1 coil terminals
(see relay schematic)
Ohmmeter on R x 10
scale
If functional, approximately 270 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
K2 Relay Coil
K2 coil terminals
(see relay schematic)
Ohmmeter on R x 10
scale
If functional, approximately 270 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
K3 Relay Coil
K3 coil terminals
(see relay schematic)
Ohmmeter on R x 10
scale
If functional, approximately 400 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
K4 Relay Coil
K4 coil terminals
(see relay schematic)
Ohmmeter on R x 10
scale
If functional, approximately 125 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
K5 Relay Coil
K5 coil terminals
(see relay schematic)
Ohmmeter on R x 10
scale
If functional, approximately 510 ohms.
Low resistance (continuity), shorted coil.
High resistance, open coil.
Figure 6-2
Relay Testing
Summary of Contents for 10EOR
Page 10: ...10 Safety Precautions and Instructions TP 6073 4 06 Notes...
Page 12: ...TP 6073 4 06 12 Service Assistance Notes...
Page 22: ...TP 6073 4 06 22 Section 3 Intake and Exhaust System Notes...
Page 26: ...TP 6073 4 06 26 Section 4 Fuel System Notes...
Page 30: ...TP 6073 4 06 30 Section 5 Cooling System Notes...
Page 38: ...TP 6073 4 06 38 Section 6 Controller Troubleshooting Notes...
Page 54: ...TP 6073 4 06 54 Section 8 Component Troubleshooting Notes...
Page 60: ...TP 6073 4 06 60 Section 9 Generator Disassembly Reassembly Notes...
Page 82: ...TP 6073 4 06 82...
Page 83: ...TP 6073 4 06 83...