154
Service
Menu item
Remark
Specifying the current for outputs 1 and 2:
Select OUT1 or OUT2 using the
keys, press enter
to confirm.
Enter a valid current value for the respective output
using
keys.
Confirm by pressing enter.
For checking purposes, the actual output current is
shown in the bottom right corner of the display.
Exit by pressing enter or meas.
Relay test (manual test of contacts):
Select RELAIS using
, press enter to confirm.
Now the status of the 4 relays is “frozen“. The 4 digits
of the main display represent the respective states
(from left to right: REL1, REL2, ALARM, WASH).
The digit for the selected relay blinks.
Select one of the 4 relays using the
keys,
close (1) or open (0) using the
keys.
Exit by pressing enter.
The relays will be re-set corresponding to the
measured value.
Press meas to return to measurement.