6. Novar-1414 Description
6.1 Basic Operation
Despite of other models, this controller model has three current measurement inputs ( one voltage
measurement input only stays unchanged ). It is capable to measure load of all three phases and
evaluates three-phase power factor for the control. Therefore, it is suitable especially for applications
with great or variable load unbalance.
The following section of the manual therefore only deals with features and operations different from
Novar1214. The other features are the same as those of Novar1214.
6.2 Measurement Values
The controller measures current in all three phase wires and evaluates appropriate phase power
factors. But one (phase or line) voltage signal is measured only – therefore it supposes that other two
voltages magnitudes are the same.
From individual phase power factors it calculates three-phase power factor, that is essential for power
factor control.
6.2.1 Main Branch
Main network values according the table 6.1 can be listed on the instrument display.
Tab. 6.1 : List of the Novar-1414 Measurement Quantities – Main Branch
abbreviation
quantity
unit
cos
Instantaneous power factor. The value corresponds to the ratio of
instantaneous active component to instantaneous total power
fundamental harmonic value in the power system. A positive value
means inductive power factor, negative means capacitive power factor.
-
Ieff
Average value of instantaneous current effective values I1, I2, I3
(including higher harmonic components).
A / kA *
Ueff
Instantaneous voltage effective value in the power system (including
higher harmonic components). By default shown in volts. If the
measurement voltage is connected via a metering transformer, in
kilovolts (see description of parameter 17).
V (kV)
* … in A as default; flashing decimal point indicates value in kA
Despite of other models, the
Ieff
value in the main branch contains average value of instantaneous
currents of individual phases L1, L2 and L3 according to formula
I
eff
=
3
I3
I2
I1
eff
eff
eff
+
+
[ A ]
[ 6 ]
6.2.2 COS Branch
Additional individual single-phase power factors
cos1
,
cos2
a
cos3
can be checked in „the Cos“ side
branch. Other quantities are the same as at standard models.
Summary of Contents for NOVAR-1 Series
Page 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Page 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Page 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Page 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Page 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Page 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...