Novar 1xxx
KMB systems
12
Table 1.3: List of Measurement Quantities – A Branch
abbreviation
symbol
quantity
unit
Iact
ACt
ACt
ACt
ACt
Instantaneous active current fundamental harmonic component
(
act
ive).
A / kA *
Irea
reA
reA
reA
reA
Instantaneous reactive current fundamental harmonic component
(
rea
ctive);
L
indicates inductive,
C
indicates capacitive polarity.
A / kA *
dIrea
dreA
dreA
dreA
dreA
Instantaneous reactive current fundamental harmonic component
difference to achieve the target power factor in the power system
(
D
elta
rea
ctive).
A / kA *
THDI
tHd
tHd
tHd
tHd
Instantaneous level of power system current’s total harmonic
distortion (
T
otal
H
armonic
D
istortion) – shows the ratio of current
higher harmonic components content, up to the 19
th
harmonic, to the
level of fundamental harmonic. It is only evaluated if the total power
system load is at least 5% of the nominal load in terms of current
determined by the metering current transformer conversion primary
side value (parameter 12).
%
3. ÷ 19.har
H-3
H-3
H-3
H-3
÷
19
19
19
19
Instantaneous current harmonic component level in the power
system.
%
maxTHDI
MtHd
MtHd
MtHd
MtHd
Maximum THDI value achieved since last clear. The evaluation is
based on THDI one-minute moving averages.
%
* … in A as default; flashing decimal point indicates value in kA
1.9.1.2.3 V Branch
This branch shows all the quantities related to voltage. They are commonly used quantities. Only the
Capacitor Harmonic Load,
CHL
, factor needs further explanation – details to be found in chapter 4.9
further below.
The maximum values can be cleared manually. Clearing any of these values clears all the other
maximum values within this branch.
Table 1.4: List of Measurement Quantities – V Branch
abbreviation
symbol
quantity
unit
F
F
FF
F
Instantaneous voltage fundamental harmonic component
frequency.
Hz
CHL
CHL
CHL
CHL
CHL
Instantaneous value of Capacitor Harmonic Load factor (
C
apacitor
H
armonic
L
oad).
%
THDU
tHd
tHd
tHd
tHd
Instantaneous level of power system voltage’s total harmonic
distortion (
T
otal
H
armonic
D
istortion) – shows the ratio of current
higher harmonic components content, up to the 19
th
harmonic, to
the level of fundamental harmonic.
%
3. ÷
19.har
H-3
H-3
H-3
H-3
÷
19
19
19
19
Instantaneous level of harmonic component voltage in the power
system.
%
maxCHL
MCHL
MCHL
MCHL
MCHL
Maximum CHL value achieved since last clear. The evaluation is
based on CHL one-minute moving averages.
%
maxTHDU
MtHd
MtHd
MtHd
MtHd
Maximum THDU value achieved since last clear. The evaluation is
based on THDU one-minute moving averages.
%
3. ÷ 19.
maxharI
MH-3
MH-3
MH-3
MH-3
÷
19
19
19
19
Maximum value of voltage harmonic component achieved since
last clear. The evaluation is based on harmonic component one-
minute moving averages.
%
Summary of Contents for NOVAR-1 Series
Page 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Page 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Page 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Page 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Page 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Page 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...