Table 5.1: Novar1312 Parameters
#
name
range
step
default
comment
0
parameter edit enable/disable
0 / 1
—
1
see Enable / Disable Parameter Editing
1
target power factor (metering rate
1)
0.80 L ÷ 0.80 C
0.01
0.98 L
2
contactor group control time on
undercompensation (met. rate 1)
5 sec ÷ 20 min
—
3 min
No “L”: control time reduction by squared
proportion
“L”: linear control time reduction.
3
contactor group control time on
overcompensation (met. rate 1)
5 sec ÷ 20 min
—
30 sec
No “L”: control time reduction by squared
proportion
“L”: linear control time reduction
4
contactor group control bandwidth 0.000 ÷ 0.040
0.005
0.010
6
metering rate 2 enable/disable
0 – 1 – E
—
0
7
÷
10
like parameters 1 ÷ 4, but for
metering rate 2
the same as
parameters 1 ÷ 4
—
—
Not displayed if metering rate 2 is
disabled (parameter 6 = 0)
12 metering current transformer
primary side nominal value
5 ÷ 9950 A
5
none
13 metering current transformer
secondary side nominal value
1 A ÷ 5 A
—
5
14 contactor group reconnection
delay time
5 sec ÷ 20 min
—
20 sec
15 type of measurement voltage –
phase or line
LN (phase) – LL
(line)
—
LN
This parameter’s correct setting is
essential for automatic connection
configuration detection process
16 method of connection of U and I
6 combinations
—
none
see parameter description
17 voltage transformer turns ratio
direct or 10 ÷ 5000 —
--- (direct)
ratio of metering voltage transformer
nominal primary voltage to nominal
secondary voltage
18 compensation system nominal
voltage U
NOM
50 ÷ 750 V x VT
turns ratio
—
230 / 400
V
controller establishes this value within the
automatic connection configuration
detection process
20 automatic section power
recognition process
A (auto) – 0 (no) –
1 (yes)
—
A
21 contactor group switching
program
12 typical
combinations
—
none
0 means individual section setting. Not
shown if automatic section power
recognition process is enabled.
22 contactor group smallest
capacitor nominal power (C/k
MIN
)
(0.007 ÷ 1.3 kvar)
x CT turns ratio x
VT turns ratio
0.001
none
Value corresponds to U
NOM
specified
(parameter 18). Not shown if automatic
section power recognition process is
enabled.
23 number of capacitors in contactor
group
1 ÷ 14
—
14
Not shown if automatic section power
recognition process is enabled.
25 each section nominal power
(0.001 ÷ 5.5 kvar)
x CT turns ratio x
VT turns ratio
0.001
none
Value corresponds to U
NOM
specified
(parameter 18).
Positive for capacitor sections, negative
for choke sections.
26 fixed sections
regulated or
0 / 1 / F / H
—
all
regulated
„F“,/ „H“ for 2 highest sections only
27 choke compensation power factor
limit
0.80 L ÷ 0.80 C
0.01
none
If not specified, compensation by choke
does not take place.
28 number of capacitors in thyristor
group
1 ÷ 12
—
0
It must always be specified manually. The
controller keeps the value specified on
initialization.
29 thyristor group control rate and
reconnection delay time
1 ÷ 20 control
interventions per
second / 0.1 ÷ 10
seconds
—
1 per
second /
10
seconds
In effect for thyristor group only.
30 alarm setting
0 / indication only /
actuation only /
indication and
actuation
—
ind. & act.
from
undercurre
nt, voltage
loss or
section
error
1... undercurrent
2... overcurrent
3... voltage loss
4... undervoltage
5... overvoltage
6... THDI >
7... THDU >
8… CHL >
9… compensation
error
10… export
11… no. of conn.’s >
12… section error
13… overheated
14… external alarm
Summary of Contents for NOVAR-1 Series
Page 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Page 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Page 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Page 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Page 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Page 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...