Novar 1xxx
KMB systems
51
This factor value does respect, besides respecting each harmonic component’s voltage value,
distribution of harmonic components of different orders across their spectrum and it addresses the
effect of voltage values. It is thus a more convenient value to determine total load of a capacitor by
current. If the nominal value voltage is undistorted, this factor is at value of 100%. The following table
shows CHL factor values for a few selected scenarios of harmonic distribution at fundamental
harmonic component nominal value.
Table 4.9: Examples of CHL factor values for selected distributions of voltage harmonic components
(U
1
=U
NOM
)
No.
voltage harmonic component levels [ % ]
CHL
3
rd
5
th
7
th
9
th
11
th
13
th
15
th
17
th
19
th
[ % ]
1
2.5
3.5
2.5
1.0
2.0
1.5
0.8
1.0
0.5
110
2
3.5
4.5
3.5
1.2
2.5
2.0
1.0
1.5
1.0
118
3
5.0
6.0
5.0
1.5
3.5
3.0
0.5
2.0
1.5
133
4
5.5
6.5
5.5
2.0
4.0
4.0
1.8
2.3
1.8
146
5
8.0
9.0
8.0
6.0
7.0
7.0
2.3
4.0
3.5
208
Example 3 (CHL = 133%) corresponds to voltage harmonic distortion limits as specified in EN 50160.
Summary of Contents for NOVAR-1 Series
Page 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Page 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Page 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Page 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Page 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Page 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...