Capacitive sections are shown as positive, inductive sections as negative values. If a section’s current
is not known (for example because of successful completion of the automatic section power
recognition process), the
----
value is shown. In such an event, as well as in the event of section
current zero value, the controller does not use the corresponding control output.
The controller is shipped with default setting of the automatic section power recognition process
enabled (parameter 20 set to A). The automatic section power recognition process is started on
introducing the power supply voltage, and after the process is complete, you can check or edit the
recognized currents in the side branch of parameter 25.
Each section’s nominal power can be changed even if it has been entered manually using the
switching program and smallest capacitor current (parameters 21, 22).
If a section’s value is shown with a flashing decimal point, it means:
•
decimal point flashing
slowly
(about once a second), the section has not been accurized yet –
see description of the mechanism to accurize sections in the relevant chapter further below
•
decimal point flashing
fast
(about three times a second), the section has been disabled and the
controller is not using it – see description of the mechanism to section disablement in the
relevant chapter further below
If you change the U
NOM
value (parameter 18), the controller will keep the actual section power value
(for example from the latest automatic section power recognition process), only their displayed
nominal
value, reflecting the changes to U
NOM
, will change.
4.1.17 Parameter 26 – Fixed Sections, Switching Cooling and Heating, Alarm
Any controller output can be set as fixed. In such a situation the output is permanently connected or
disconnected. The two highest outputs can further be used to switch cooling and heating, and in case
of Novar 10xx models for alarm signalling too. The controller does not use sections set up this way for
power factor control.
4.1.17.1 Fixed Sections
A fixed output
maintains its preset condition
(that is connected or disconnected) with the following
exceptions:
•
the controller is switched to the
Manual
mode
•
a selected nonstandard condition occurs while the alarm’s corresponding actuation
function has been set (for details see alarm description further below)
A fixed section (one set as permanently connected) is
only
disconnected if the alarm has been
activated because of crossing over the threshold level of the quantity selected for a specified time (for
details see description of alarm functions further below).
By default all controller’s outputs are set as controlled, not fixed. In such an event they are shown for
example as follows:
01-C
01-C
01-C
01-C
.... output 1 is controlled and it is a capacitive section (capacitor)
12-L
12-L
12-L
12-L
.... output 12 is controlled and it is an inductive section (choke)
Each section’s value can be set to
0
00
0
or
1
11
1
,
that is
01-0
01-0
01-0
01-0
or
01-1
01-1
01-1
01-1
, respectively, is displayed
and the corresponding output becomes a fixed one – it stays permanently disconnected or
permanently connected.
Summary of Contents for NOVAR-1 Series
Page 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Page 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Page 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Page 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Page 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Page 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...