Novar 1xxx
KMB systems
41
4.1.20 Parameters 31 through 37 – Alarm Indication/Actuation Limits
If indication or actuation from a condition shown in Table 4.7 is set up, you also need to specify the
relevant quantity’s limit value exceeding which triggers the indication or actuation. The table shows
parameter numbers where the limits are stored, limit setup ranges, and limit default values.
Number of switching operations limit (parameter 36) is shown in thousands.
If neither indication nor actuation from either of the two conditions has been set, the corresponding
limit value is not shown.
Table 4.6: Alarm – actuation
#
condition
minimum delay of
activation / deactivation
actuation
1
undercurrent
10 / 5 seconds
disconnection of all sections
except fixed ones
3
voltage failure
immediately / 5 seconds
disconnection of all sections
4 undervoltage
maximum 1 minute (depends
on the extent of
undervoltage)
disconnection of all sections
5 overvoltage
maximum 1 minute (depends
on the extent of overvoltage)
disconnection of all sections
6 THDI >
maximum 1 minute (depends
on the level of THDI)
disconnection of all sections
7 THDU >
maximum 1 minute (depends
on the level of THDU)
disconnection of all sections
8 CHL >
maximum 1 minute (depends
on the level of CHL)
disconnection of all sections
10 power export
maximum 1 minute (depends
on the level of active power)
disconnection of all sections
except fixed ones
12
section error
5 conne
5 disconnections
section disablement (see
description in chapter below)
13 overheated
maximum 1 minute (depends
on the level of temperature)
disconnection of all sections
14 external alarm
immediately / 5 seconds
disconnection of all sections
Note: Conditions shown above in bold type are set by default.
Table 4.7: Alarm Limits
#
condition
limit –
parameter
number
limit setup range
standard
value
4 undervoltage
31
50 ÷ 100 % U
NOM
(par. 18)
80 %
5 overvoltage
32
100 ÷ 200 % U
NOM
(par. 18)
110 %
6 THDI >
33
1 ÷ 300 %
20 %
7 THDU >
34
1 ÷ 300 %
10 %
8 CHL >
35
80 ÷ 300 %
130 %
11 number of
switching
operations
exceeded
36
10 ÷ 2000 x thousand of switching
operations
1000
13 overheated
37
20 ÷ 60 °C
45 °C
Summary of Contents for NOVAR-1 Series
Page 66: ...Novar 1xxx KMB systems 66 Novar1106 installation...
Page 67: ...Novar 1xxx KMB systems 67 Novar1114 installation...
Page 68: ...Novar 1xxx KMB systems 68 Novar1206 installation low voltage measurement...
Page 69: ...Novar 1xxx KMB systems 69 Novar1214 installation high voltage measurement...
Page 70: ...Novar 1xxx KMB systems 70 Novar1114 S400 installation...
Page 73: ...Novar 1xxx KMB systems 73 Novar1414 installation low voltage measurement...