WOOD BURNING BOILER COOKER ALTEA 110 SICURO TOP
28
EN - Rev. 1.2
What happens if there is..
-
INSUFFICIENT DRAUGHT
-
POOR FLUE GAS EVACUATION
-
FLUE GAS ESCAPING INTO THE ROOM
ELEMENTS TO CHECK
ORIGIN
External air intake
-
Non-existent;
-
Shutter closed;
-
Accidental obstruction;
-
Insufficient cross section.
Air intake (pipe)
-
Insufficient cross section.
Combustion air damper
-
Closed or incorrectly set.
Smoke damper
-
Closed or incorrectly set.
Wood
-
Excessive humidity.
Flue
Hood fitting/flue gas channel
-
Insufficient cross section;
-
Insufficient height;
-
Accidental obstructions;
-
Periodical cleaning not performed;
-
Heat insulation or insulation insufficient or non-existent;
-
Use of unsuitable materials;
-
Heat insulation or insulation absent or insufficient;
-
Inadequate cross section (square or rectangular) or incorrectly sized;
-
Narrowing or presence of obstacles to the flow of flue gas;
-
Accidental obstructions;
-
Infiltrations of parasite air due to the use of materials not impermeable
to gas and liquids;
-
Insufficient height.
Chimney
-
Outlet height in the reflux zone;
-
Close to or adjoining other chimneys;
-
Vicinity of obstacles, both natural and artificial;
-
Obstruction ( e.g.: birds nests);
-
Inadequate chimney pot shape;
-
Insufficient emission cross section.
-
CONDENSATE ESCAPING THROUGH THE MASONRY
ELEMENTS TO CHECK
ORIGIN
Flue gas channel
Flue
Condensate tray
-
Use of inadequate material;
-
Absence of or incorrect installation of the dedicated condensate
collector with drain connected to the disposal system.
-
SELF-COMBUSTION INSIDE THE FLUE
ELEMENTS TO CHECK
ORIGIN
Hood fitting/flue gas channel
Flue gas channel
Flue
-
Periodical cleaning not performed.
-
WATER INSIDE THE COMBUSTION CHAMBER AND/OR THE ASH DRAWER
ELEMENTS TO CHECK
ORIGIN
Flue
Chimney
-
In the event of the total or partial absence of a chimney, the flue has not
been installed parallel to the appliance;
-
Unsuitable chimney.
Pump thermostat
-
Pump start-up at temperatures that are too low (condensate is created).