Parameters
Symbol
Min
Factory
setting
Max
Recommended
values
Reference led
PUMP thermostat
A01
50 °C
55 °C
85 °C
Minimum 55 °C
L1
VALVE thermostat
A02
20 °C
65 °C
85 °C
65 °C
(only if connected)
L2
AUX thermostat
A03
20 °C
85 °C
85 °C
50 °C
(only if connected)
L3
SERV thermostat
A04
20 °C
85 °C
85 °C
60 °C
(only if connected)
L7
FAULT SIGNALLING AND ALARMS
The control unit signals faults associated with the
H2O PROBE
via a flashing message:
-
Lo
: indicates a value below the set scale (temperature below 0°C).
Occurs when the H2O PROBE is off
.
-
Hi
: indicates a value above the set scale (temperature above 100°C).
Occurs when the H2O PROBE has had a short circuit.
PARAMETER SETTINGS
PROGRAMMABLE PARAMETERS
ANTIFREEZE activation thermostat
[°C]
6
SAFETY activation thermostat
[°C]
85
ALARM function activation thermostat
[°C]
90
PUMP thermostat hysteresis (A01)
[°C]
3
VALVE thermostat hysteresis (A02)
[°C]
3
AUX thermostat hysteresis (A03)
[°C]
3
SERV thermostat hysteresis (A04)
[°C]
3
ANTILOCKING timer
[h]
168
ANTILOCKING pump activation time
[sec]
30
ANTIFREEZE Pump OFF time
[min]
5
ANTIFREEZE Pump ON time
[sec]
20
Type of Probes (10K blue=’0’
-
100K grey= ‘1’)
no.
0
STANDBY enabling
no.
1
ANTIFREEZE function enabling
no.
1
NON-PROGRAMMABLE PARAMETERS
ANTIFREEZE thermostat hysteresis
[°C]
1
SAFETY thermostat hysteresis
[°C]
1
ALARM thermostat hysteresis
[°C]
1