KLINGER Denmark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | [email protected] | www.klinger.dk
Klinger CMF
Instruction Manual
Page 57
110
1242
Double component
calculation temp. pt.1
-50~400
Read and Write
/0.00
111
1244
Double component
calculation temp. pt.2
-50~400
Read and Write
/0.00
112
1246
Double component
calculation temp. pt.3
-50~400
Read and Write
/0.00
113
1248
Double component
calculation temp. pt.4
-50~400
Read and Write
/0.00
114
1250
Double component
calculation temp. pt.5
-50~400
Read and Write
/0.00
115
1252
Group A temp. pt.1
density
0~3.0000
Read and Write
/0
116
1254
Group A temp. pt.2
density
0~3.0000
Read and Write
/0
117
1256
Group A temp. pt.3
density
0~3.0000
Read and Write
/0
118
1258
Group A temp. pt.4
density
0~3.0000
Read and Write
/0
119
1260
Group A temp. pt.5
density
0~3.0000
Read and Write
/0
120
1262
Group B temp. pt.1
density
0~3.0000
Read and Write
/0
121
1264
Group B temp. pt.2
density
0~3.0000
Read and Write
/0
122
1266
Group B temp. pt.3
density
0~3.0000
Read and Write
/0
123
1268
Group B temp. pt.4
density
0~3.0000
Read and Write
/0
124
1270
Group B temp. pt.5
density
0~3.0000
Read and Write
/0
125
1272
Group A volume ratio
0~100.00
Read Only
126
1274
Group A mass ratio
0~100.00
Read Only
127
1276
Error code
Bit0~Bit4
Read and Write
/0
6.2.2.1 Each register has 4 bytes, occupying two addresses (low address addressing), and data
transfer using 32 single precision floating point number (high byte in front).
6.2.2.2 Grey shaded parameters
(
23~24,36~47,61~106
)
are Manufacturer parameters,
which have been optimized before delivery, do not modify these values! Parameters
written in red text
(
23~24,42~47,76~81,93,95~96,107~108
)
t can be Accessed and
modified only through Modbus communication, and are not available through the
standard user interface.
6.2.3 Configuration
6.2.3.1 Mass flow unit
The codes for the various mass flow rate units are defined in table 6-2.
Table 6-2 mass flow rate units
Code
0
1
2
3
4
5
6
7
Unit
g/s
g/min
g/h
kg/s
kg/min
kg/h
kg/day
t/s
Code
8
9
10
11
12
13
14
Unit
t/min
t/h
t/day
lb/s
lb/min
lb/h
lb/day
6.2.3.2 Volumetric flow unit
The codes for the various volumetric flow rates units are defined in table 6-3.