Klinger CMF
Instruction Manual
Page 27
Chapter
Software operation guide of the
transmitter
5.1 Operation panel
Operation panel of mass flow meter transmitter- See figure 5-1
Figure 5-1 Operation panel of mass flowmeter transmitter
5.1.1 Touch keys
5.1.1.1 There are four touch keys on the Transmitter operation panel:
Up: Scroll up, or increment the selected value.
Down: Scroll down or reduce the selected value.
Function: Activate the selected function.
Cancel: Back out of the current selection or menu.
5.1.1.2 Symbol description of status indicator area
: Keys are locked.
: Keys are unlocked.
0
: The filtering coefficient is less than 0.21 and the absolute value of the phase
difference is greater than 0.020us therefore zero calibration is necessary.
: The filtering coefficient is less than 0.21 and the absolute value of the phase difference
is between 0.020us and 0.015us therefore zero calibration is recommended.
0 0
: A measured variable (either the primary or secondary display) is out of the range of
the display. Adjust the display units.
5.1.1.3 Key operation
Touching the glass in front of key just like figure 5-2, the red indicator aside will light if
operation is ok.