81
300
600
A_ComSupFC
Alarm of no communication with supply inverter
0 – no alarm, 1 – alarm
BV
Coil 9600
R
301
602
A_ComSupFC2
Alarm of no communication with supply inverter 2
0 – no alarm, 1 – alarm
BV
Coil 9632
R
302
604
A_ComExhFC
Alarm of no communication with exhaust inverter
0 – no alarm, 1 – alarm
BV
Coil 9664
R
303
606
A_ComExhFC2
Alarm of no communication with exhaust inverter 2
0 – no alarm, 1 – alarm
BV
Coil 9696
R
304
608
A_Tsup
Supply temperature sensor alarm
0 – no alarm, 1 – alarm
BV
Coil 9728
R
305
610
A_Texh
Exhaust temperature sensor alarm
0 – no alarm, 1 – alarm
BV
Coil 9760
R
306
612
A_Tout
External temperature sensor alarm
0 – no alarm, 1 – alarm
BV
Coil 9792
R
307
614
A_Trec
Alarm of the exhaust temperature sensor downstream the recuperation
0 – no alarm, 1 – alarm
BV
Coil 9824
R
308
616
A_TsupPrim Alarm of the supply temperature sensor downstream the main heater
0 – no alarm, 1 – alarm
BV
Coil 9856
R
309
618
A_TbackWater
Alarm of the return water temperature sensor from the water heater
0 – no alarm, 1 – alarm
BV
Coil 9888
R
310
620
A_Tmain
Master temperature sensor alarm
0 – no alarm, 1 – alarm
BV
Coil 9920
R
311
622
A_InEmul Controller input emulation alarm
0 – no alarm, 1 – alarm
BV
Coil 9952
R
312
624
A_OutForce Controller output forcing alarm
0 – no alarm, 1 – alarm
BV
Coil 9984
R
313
626
Alarm
Collective alarm
0 – no alarm, 1 – alarm
BV
Coil
10016
R
10.2 Bacnet MS-TP communication with the BMS system
Search for BacNet variables after connecting the
switched on controller and implementing appropriate
BacNet network settings.
10.3 Control via WWW
The controller can be managed via www protocol.
The shown below optional Ethernet adapter is required
as a hardware element:
Fig. 9
Location for instal ETH module
To connect from a local PC connected directly with
cable with the controller’s ETH adapter:
1. Input the following values in the settings of the PC’s
network adapter for the TCP4 protocol:
Fig. 10
Network module settings of the PC for TCP4 protocol
2. Then open the Internet browser and enter the default
controller address: 192.168.0.8. The window appears
– please enter default login: admin and password: admin
Fig. 11
Login window and access passwords
3. When the login and password are entered and the
login is validated, the controller’s HMI screen appears.
Here you can change the settings and view all control-
ler menu options.
Fig. 12
Controller HMI graphic screen
Fig. 13
AHU visualisation screen
ETH module with RJ connector
Summary of Contents for EVO -T
Page 2: ...SERWIS SERVICE 48 587839950 51 48 587839888 48 510098081 serwis klimor com...
Page 39: ...37...
Page 41: ...39...
Page 55: ...53 NOTATKI...
Page 56: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 91: ...89 CONTROL AUTOMATION CONTROL...
Page 107: ...105 NOTES...
Page 108: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 109: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Page 115: ...113 5 7 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Page 145: ...143 26 2S 27 2S...
Page 146: ...144 EVO T EVO T COMPACT 28 EH M 18kW 1 PE_ PE_ Max 18...
Page 147: ...145...
Page 148: ...146 EVO T EVO T COMPACT 29 EH M 36 kW 3 Max 12 Max 12 Max 12 PE_ 0 5mm2 blue 0 5mm2 white...
Page 149: ...147 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2...
Page 150: ...148 EVO T EVO T COMPACT 30 4S 31 4S...
Page 155: ...153 1 2 3 40 15 1 8 HMI HMI OK C HMI 15 1 9 HMI 3 C Alarms history 41 42...
Page 161: ...159 16...
Page 162: ...160 EVO T EVO T COMPACT...
Page 163: ......