71
Group
Name
Default
value
Description / Settings menu
Fans
-
10 s
Switch on delay – time between starting the dampers and starting the fans.
15 s
Damper switch off delay – time between stopping the fan and stopping the dampers.
30 s
Pressure gauge delay – time from starting the fans after which filter pressure is measured.
Cooling
30 s
Cooling down time – time from switching "Operation in 1st, 2nd, 3rd speed" operation mode into "Stop" operation mode and stopping
operation of the electric heater or/and DX cooler till stopping the fans.
100%
Air supply – air supply fans capacity during cooling down
100%
Air exhaust – air exhaust fans capacity during cooling down
RS 485
Inactive
Air supply inverter RS485 – activation of communication with the air supply fan inverter/ EC controller
Inactive
Air supply inverter 2 RS485 – activation of communication with the secondary air supply fan inverter/EC controller
Inactive
Air exhaust inverter RS485 – activation of communication with the air exhaust fan inverter/EC controller
Inactive
Air exhaust inverter 2 RS485 – activation of communication with the secondary air exhaust fan inverter/EC controller
1
Air supply inverter address – air supply fan inverter/EC controller address
2
Air supply inverter 2 address – secondary air supply fan inverter/EC controller address
3
Air exhaust inverter address – air exhaust fan inverter/EC controller address
4
Air exhaust inverter 2 address – secondary air exhaust fan inverter/EC controller address
70%
Min air supply airflow – setting of the 1st speed airflow
85%
Medium air supply airflow – setting of the 2nd speed airflow
100%
Max air supply airflow – setting of the 3rd speed airflow
70%
Min air exhaust airflow – setting of the 1st speed airflow
85%
Medium air exhaust airflow – setting of the 2nd speed airflow
100%
Max air exhaust airflow – setting of the 3rd speed airflow
60s
Acceleration time – inverters start-up time
60s
Stopping time – inverters stopping time
0.3s
Tcom – time of communication with the inverter
3s
Twait – response awaiting time in communication with the inverter
Regula
tion
adjustmen
t
-
20%
Heat recovery adjustment part (editable parameter)
20%
Mixing chamber adjustment part (editable parameter)
...%
Heater/cooler adjustment part (read-only parameter)
Con
trollers
1
Kp_grzania – gain of heater controller
60s
Ti_grzania – integration constant of heater controller
1
Kp_chłodzenia – gain of cooler controller
60s
Ti_chłodzenia – integration constant of cooler controller
Summer/
Winter
PI chłodzenia – possibility to activate the cooling controller only in summer or summer and winter
30s
Opóźnienie załączenia – possibility to make a delay switching setting for the cooling controller
1
Kp_nawiewu – gain of air supply controller
45s
Ti_nawiewu – integration constant of air supply controller
40°C
Tmax – maximum supply temperature (cascade controller)
15°C
Tmin – minimum supply temperature (cascade controller)
...°C
TsetBlowAct – the current supply setpoint temperature (cascade controller)
Recovery
-
450 s
Starting ramp – once the system is started, the 100% heat recovery is started with dropping ramp till current heat recovery actuation
resulting from the adjustment process
2°C
Frosting limit – temperate below which the anti-frost function is activated
1
Kp_zwalniania – gain of ant-frost function controller
30s
Ti_zwalniania – integration constant of ant-frost function controller
Summary of Contents for EVO -T
Page 2: ...SERWIS SERVICE 48 587839950 51 48 587839888 48 510098081 serwis klimor com...
Page 39: ...37...
Page 41: ...39...
Page 55: ...53 NOTATKI...
Page 56: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 91: ...89 CONTROL AUTOMATION CONTROL...
Page 107: ...105 NOTES...
Page 108: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 109: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Page 115: ...113 5 7 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Page 145: ...143 26 2S 27 2S...
Page 146: ...144 EVO T EVO T COMPACT 28 EH M 18kW 1 PE_ PE_ Max 18...
Page 147: ...145...
Page 148: ...146 EVO T EVO T COMPACT 29 EH M 36 kW 3 Max 12 Max 12 Max 12 PE_ 0 5mm2 blue 0 5mm2 white...
Page 149: ...147 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2...
Page 150: ...148 EVO T EVO T COMPACT 30 4S 31 4S...
Page 155: ...153 1 2 3 40 15 1 8 HMI HMI OK C HMI 15 1 9 HMI 3 C Alarms history 41 42...
Page 161: ...159 16...
Page 162: ...160 EVO T EVO T COMPACT...
Page 163: ......