61
5. DESCRIPTION OF SYSTEM OPERATION
Table no. 7
Functions of AHU systems
Function
Actuation condition
Description of operation
Fan start
Set the operation mode
Speed 1, Speed 2, Standby, Timer
- External dampers open
- Turning on the air supply fan’s motor (air supply AHUs) or air supply/exhaust fans’ motors (air supply/exhaust AHUs)
Temper
atur
e adjustmen
t
Description
Set the operation mode
Speed 1, Speed 2, Standby, Timer
- Comparison of current temperature measured with the master sensor with the set value entered in the control-
ler as well as actuation of heat/cool exchangers
- Limiting of min and max temperature of supply air
Hea
ting
Water heater
Master adjustment sensor tem-
perature is below the set tem-
perature
- Increasing the medium (water or glycol solution) flow rate through the water heating coil
- Activation of anti-frost function if the temperature downstream the heater (thermostat) is too low
Electric heater
- Stepless power increase of the electric heater
- Cooling down the heater while switching from run into stop mode
- Monitoring of heater overheating with the thermostat
Cooling
Water cooling
coil
Master adjustment sensor tempe-
rature is above the set temperature
- Increasing the medium (water or glycol solution) flow rate through the cooler
DX cooling coil
- Switching on the 1st, 2nd stage of the compressor unit
- Cooling system initiation lock applied at low external temperatures (factory setting: 13°C)
- Min. time of compressor operation (even if the initiation signal is not fed) and min break time (even if the
initiation signal is fed)
Ener
gy
rec
ov
er
y syst
ems
Heat recovery
Set the operation mode
Speed 1, Speed 2, Standby,Timer
External temperature is 1K lower
than air exhaust sensor tempe-
rature
- Initiation of the recovery system (START/STOP)
- Activation of anti-frost function of the heat recovery system at low air exhaust temperature, downstream the
heat recovery (cross-flow heat recovery – closing)
Recirculation chamber
Set the operation mode
Speed 1, Speed 2, Standby, Timer
Operation in the heating sequence
- Stepless adjustment of air dampers’ opening using the actuators
- Mixing degree of the air extracted from the room with the external supplied air depends on the temperature
difference measured with the air exhaust sensor and the set temperature
- Adjustment of air mixing degree is carried out before or after the adjustment of cooling and heating devices,
depending on the priority setting for the mixing chamber or heater/cooler
- Activation of reheating function possible: if the ambient temperature is below the set temperature, the system
switches into the heating sequence, the AHUs with recirculation will operate with minimal amount of fresh air (factory
setting: min 30% external air damper opening), then the controller starts to adjust the temperature using the heater
- Manual setting possible
Summary of Contents for EVO -T
Page 2: ...SERWIS SERVICE 48 587839950 51 48 587839888 48 510098081 serwis klimor com...
Page 39: ...37...
Page 41: ...39...
Page 55: ...53 NOTATKI...
Page 56: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 91: ...89 CONTROL AUTOMATION CONTROL...
Page 107: ...105 NOTES...
Page 108: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 109: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Page 115: ...113 5 7 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Page 145: ...143 26 2S 27 2S...
Page 146: ...144 EVO T EVO T COMPACT 28 EH M 18kW 1 PE_ PE_ Max 18...
Page 147: ...145...
Page 148: ...146 EVO T EVO T COMPACT 29 EH M 36 kW 3 Max 12 Max 12 Max 12 PE_ 0 5mm2 blue 0 5mm2 white...
Page 149: ...147 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2...
Page 150: ...148 EVO T EVO T COMPACT 30 4S 31 4S...
Page 155: ...153 1 2 3 40 15 1 8 HMI HMI OK C HMI 15 1 9 HMI 3 C Alarms history 41 42...
Page 161: ...159 16...
Page 162: ...160 EVO T EVO T COMPACT...
Page 163: ......