68
AUTOMATION AND CONTROL SYSTEM FOR UNITS
EVO-T; EVO-T COMPACT
OPERATION AND MAINTENANCE MANUAL
Alarms
Alarm
type
System response, action / Alarms list
A_Trec
Blocking
Inspection of air exhaust temperature sensor operation
downstream the heat recovery:
Normal condition
– no alarm, sensor connected
Alarm condition
– alarm triggered, sensor disconnected or faulty
Response to the alarm condition: the system is stopped, check
the sensor and its connection to the ELP11R19L BAC+ controller,
determine the problem source, once the alarm source is eliminated
the alarm is reset automatically and the system resumes operation
Sensor input PT4
A_
Tsup-
Prim
Blocking
Inspection of air supply temperature sensor operation
downstream the preliminary heater (if active in ‚Service/Se-
tup/Preliminary heater/Operation permit – active’ menu):
Normal condition
– no alarm, sensor connected
Alarm condition
– alarm triggered, sensor disconnected or faulty
Response to the alarm condition: the system is stopped, check
the sensor and its connection to the ELP11R19L BAC+ controller,
determine the problem source, once the alarm source is eliminated
the alarm is reset automatically and the system resumes operation
Sensor input PT5
A_
Tbac-
kWater
Fading
Inspection of correct operation of the heater’s return water
temperature sensor:
Normal condition
– no alarm, sensor connected
Alarm condition
– alarm triggered, sensor disconnected or faulty
Response to the alarm condition: the system is stopped, check the
sensor and its connection to the controller, determine the problem
source, once the alarm source is eliminated, confirm the alarm and
start the system
Sensor input PT5
A_
Tmain
Blocking
Master temperature sensor operation inspection:
Normal condition
– no alarm, sensor connected
Alarm condition
– alarm triggered, sensor disconnected or faulty
Response to the alarm condition: the system is stopped, check the
sensor and its connection to the ELP11R19L BAC+ controller, deter-
mine the problem source, once the alarm source is eliminated the
alarm is reset automatically and the system resumes operation
The input depends on the master sensor selection
Misc Alarms
A_Com-
SupFC
Fading
Communication inspection of the controller and air sup-
ply fan inverter or EC motor controller:
Normal condition
– no alarm, correct communication
Alarm condition
– alarm triggered, incorrect communication
Response to the alarm condition: the system is stopped, check
the inverter and its connection to the ELP11R19L BAC+ control-
ler or air supply EC motor controller, find out the problem source,
once the problem is eliminated the system resumes operation
automatically.
A_Com-
SupFC2
Fading
Communication inspection of the controller and air sup-
ply fan secondary inverter or EC motor controller:
Normal condition
– no alarm, correct communication
Alarm condition
– alarm triggered, incorrect communication
Response to the alarm condition: the system is stopped, check
the inverter and its connection to the EELP11R19L BAC+ control-
ler or air supply EC motor controller, find out the problem source,
once the problem is eliminated the system resumes operation
automatically.
A_Co-
mExhFC
Fading
Communication inspection of the controller and air
exhaust fan inverter or EC motor controller:
Normal condition
– no alarm, correct communication
Alarm condition
– alarm triggered, incorrect communication
Response to the alarm condition: the system is stopped, check
the inverter and its connection to the ELP11R19L BAC+ con-
troller or air exhaust EC motor controller, find out the problem
source, once the problem is eliminated the system resumes
operation automatically.
A_Co-
mExhFC2
Fading
Communication inspection of the controller and air
exhaust fan secondary inverter or EC motor controller:
Normal condition
– no alarm, correct communication
Alarm condition
– alarm triggered, incorrect communication
Response to the alarm condition: the system is stopped, check
the inverter and its connection to the ELP11R19L BAC+ con-
troller or air exhaust EC motor controller, find out the problem
source, once the problem is eliminated the system resumes
operation automatically.
A_Lo-
wTemp
Blocking
Inspecting sufficiently high air supply temperature:
Normal condition
– no alarm, air supply temperature is maintained
above the min level
Alarm condition
– alarm triggered, air supply temperature below
preset level within defined time
Response to the alarm condition: the system is stopped, check the heat
exchangers and system operation, once the problem is eliminated
confirm the alarm and start the system.
A_Col-
dRec
Fading
Frosting inspection of heat recovery air exhaust part using
the temperature sensor:
Normal condition
– no frosting, temperature high enough
Alarm condition
– frosting present, temperature too low
Response to the alarm condition: the system operates, heat recovery
actuation is reduced, once the alarm disappears the system operates
with heat recovery if temperature adjustment is required, if the alarm
does not disappear for a longer time, check the heat recovery system
and revert it to the condition before the alarm occurred.
Sensor input PT4
Normal condition
– no frosting, pressure difference downstream and
upstream the heat recovery is lower than the one set on the pressure
gauge, no 24VAC signal at digital input
Alarm condition
– frosting present, pressure difference downstream
and upstream the heat recovery is higher than the one set on the
pressure gauge, 24VAC signal at digital input
Response to the alarm condition: the system operates, heat recovery
actuation is reduced, once the alarm disappears the system operates
with heat recovery if temperature adjustment is required, if the alarm
does not disappear for a longer time, check the heat recovery system
and revert it to the condition before the alarm occurred.
Summary of Contents for EVO -T
Page 2: ...SERWIS SERVICE 48 587839950 51 48 587839888 48 510098081 serwis klimor com...
Page 39: ...37...
Page 41: ...39...
Page 55: ...53 NOTATKI...
Page 56: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 91: ...89 CONTROL AUTOMATION CONTROL...
Page 107: ...105 NOTES...
Page 108: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 109: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Page 115: ...113 5 7 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Page 145: ...143 26 2S 27 2S...
Page 146: ...144 EVO T EVO T COMPACT 28 EH M 18kW 1 PE_ PE_ Max 18...
Page 147: ...145...
Page 148: ...146 EVO T EVO T COMPACT 29 EH M 36 kW 3 Max 12 Max 12 Max 12 PE_ 0 5mm2 blue 0 5mm2 white...
Page 149: ...147 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2...
Page 150: ...148 EVO T EVO T COMPACT 30 4S 31 4S...
Page 155: ...153 1 2 3 40 15 1 8 HMI HMI OK C HMI 15 1 9 HMI 3 C Alarms history 41 42...
Page 161: ...159 16...
Page 162: ...160 EVO T EVO T COMPACT...
Page 163: ......