79
200
400
Twait
Communication waiting time (should be set higher than multiplicity of Tcom x
number of devices engaged in communication)
1s = 256 (22s = 22*256 = 5632 = 0x1600)
AV
Register
R/W
201
402
MaxDiff
Maximum value of set point deviation and temperature from master temperature history 1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
202
404
T1
Master temperature history – measurement 1
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
203
406
T2
Master temperature history – measurement 2
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
204
408
T3
Master temperature history – measurement 3
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
205
410
T4
Master temperature history – measurement 4
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
206
412
T5
Master temperature history – measurement 5
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
207
414
T6
Master temperature history – measurement 6
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
208
416
T7
Master temperature history – measurement 7
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
209
418
T8
Master temperature history – measurement 8
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
210
420
T9
Master temperature history – measurement 9
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
211
422
T10
Master temperature history – measurement 10
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
212
424
T11
Master temperature history – measurement 11
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
213
426
T12
Master temperature history – measurement 12
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
214
428
T13
Master temperature history – measurement 13
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
215
430
T14
Master temperature history – measurement 14
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
216
432
T15
Master temperature history – measurement 15
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
217
434
HistPeriod Temperature measurement period
1s = 256 (22s = 22*256 = 5632 = 0x1600)
AV
Register
R/W
218
436
Reset
Reset of measurements from the master temperature history
0 – off 1 – on
MSV
Coil 6976
R/W
219
438
_DIN1
Readout of the state of digital input 1
0 – open, 1 – closed
MSV
Coil 7008
R
220
440
_DIN2
Readout of the state of digital input 2
0 – open, 1 – closed
MSV
Coil 7040
R
221
442
_DIN3
Readout of the state of digital input 3
0 – open, 1 – closed
MSV
Coil 7072
R
222
444
_DIN4
Readout of the state of digital input 4
0 – open, 1 – closed
MSV
Coil 7104
R
223
446
_DIN5
Readout of the state of digital input 5
0 – open, 1 – closed
MSV
Coil 7136
R
224
448
PT_1
Readout of input of sensor PT1000 1
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
225
450
PT_2
Readout of input of sensor PT1000 2
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
226
452
PT_3
Readout of input of sensor PT1000 3
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
227
454
PT_4
Readout of input of sensor PT1000 4
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
228
456
PT_5
Readout of input of sensor PT1000 5
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
229
458
HMI_Con
Readout of sensor in HMI setter connected via HMI CON connector
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
230
460
HMI_RS
Readout of sensor in HMI setter connected via RS485 connector
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R
231
462
Re1
Readout of state of digital output 1
0 – Off, 1 – On
MSV
Coil 7392
R
232
464
Re2
Readout of state of digital output 2
0 – Off, 1 – On
MSV
Coil 7424
R
233
466
Re3
Readout of state of digital output 3
0 – Off, 1 – On
MSV
Coil 7456
R
234
468
Re4
Readout of state of digital output 4
0 – Off, 1 – On
MSV
Coil 7488
R
235
470
Re5
Readout of state of digital output 5
0 – Off, 1 – On
MSV
Coil 7520
R
236
472
Re6
Readout of state of digital output 6
0 – Off, 1 – On
MSV
Coil 7552
R
237
474
AO1
Readout of state of analogue output 1
1V = 256 (22V = 22*256 = 5632 = 0x1600)
AV
Register
R
238
476
AO2
Readout of state of analogue output 2
1V = 256 (22V = 22*256 = 5632 = 0x1600)
AV
Register
R
239
478
AO3
Readout of state of analogue output 3
1V = 256 (22V = 22*256 = 5632 = 0x1600)
AV
Register
R
240
480
F_DIN1
Emulation of digital input 1
0 – no emulation, 1 – set open, 3 – set closed MSV Register
R/W
241
482
F_DIN2
Emulation of digital input 2
0 – no emulation, 1 – set open, 3 – set closed MSV Register
R/W
242
484
F_DIN3
Emulation of digital input 3
0 – no emulation, 1 – set open, 3 – set closed MSV Register
R/W
243
486
F_DIN4
Emulation of digital input 4
0 – no emulation, 1 – set open, 3 – set closed MSV Register
R/W
244
488
F_DIN5
Emulation of digital input 5
0 – no emulation, 1 – set open, 3 – set closed MSV Register
R/W
245
490
Em_PT1
Emulation of input of sensor PT1000 1
0 – inactive, 1 – active
MSV
Coil 7840
R/W
246
492
E_PT1
Emulated value of input of sensor PT1000 1
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R/W
247
494
Em_PT2
Emulation of input of sensor PT1000 2
0 – inactive, 1 – active
MSV
Coil 7904
R/W
248
496
E_PT2
Emulated value of input of sensor PT1000 2
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R/W
249
498
Em_PT3
Emulation of input of sensor PT1000 3
0 – inactive, 1 – active
MSV
Coil 7968
R/W
250
500
E_PT3
Emulated value of input of sensor PT1000 3
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R/W
251
502
Em_PT4
Emulation of input of sensor PT1000 4
0 – inactive, 1 – active
MSV
Coil 8032
R/W
252
504
E_PT4
Emulated value of input of sensor PT1000 4
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R/W
253
506
Em_PT5
Emulation of input of sensor PT1000 5
0 – inactive, 1 – active
MSV
Coil 8096
R/W
254
508
E_PT5
Emulated value of input of sensor PT1000 5
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R/W
255
510
Em_Hcon
Emulation of input of sensor in setter connected to HMI CON connector
0 – inactive, 1 – active
MSV
Coil 8160
R/W
256
512
E_Hcon
Emulated value of sensor in setter connected to HMI CON connector
1°C=256(22°C = 22*256 = 5632 = 0x1600)
AV
Register
R/W
Summary of Contents for EVO -T
Page 2: ...SERWIS SERVICE 48 587839950 51 48 587839888 48 510098081 serwis klimor com...
Page 39: ...37...
Page 41: ...39...
Page 55: ...53 NOTATKI...
Page 56: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 91: ...89 CONTROL AUTOMATION CONTROL...
Page 107: ...105 NOTES...
Page 108: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 109: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Page 115: ...113 5 7 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Page 145: ...143 26 2S 27 2S...
Page 146: ...144 EVO T EVO T COMPACT 28 EH M 18kW 1 PE_ PE_ Max 18...
Page 147: ...145...
Page 148: ...146 EVO T EVO T COMPACT 29 EH M 36 kW 3 Max 12 Max 12 Max 12 PE_ 0 5mm2 blue 0 5mm2 white...
Page 149: ...147 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2 0 5mm2...
Page 150: ...148 EVO T EVO T COMPACT 30 4S 31 4S...
Page 155: ...153 1 2 3 40 15 1 8 HMI HMI OK C HMI 15 1 9 HMI 3 C Alarms history 41 42...
Page 161: ...159 16...
Page 162: ...160 EVO T EVO T COMPACT...
Page 163: ......