Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
37
4.12 Signal Interface:
•
The control signal input port is a 2Pin port. It can execute corresponding commands in short
circuit, as shown in the following figure.
Fig 7 Remote Control Signal Port
Input dry contacts:
ID
Name
Control mode System actions description
BAT.TEMP
Battery
temperature
Sensing
Perform charging compensation by battery
temperature coefficient
BAT.TEST
Battery self-
test
Short circuit ≥
0.2 s
The Energy Server performs battery test
INV ON
Energy Server
power ON
In standby mode, system power ON
INV OFF
Energy Server
power Off
In power-ON mode, system power OFF
FAULT CLEAR
Fault clear
Clear
executed
abnormal
protection
commands and restart the Energy Server.
EPO
Emergency
power off
Energy Server responds to the EPO command
and interrupts output
Table 16 Input Dry Contacts Description
•
The output signal port (dry contact) is a 3Pin port, therefore users can select
“
Normally open
”
mode or
“
Normally closed
”
mode according to the needs of the site (as shown in the following
figure).