Over Temp
System
high-temperature
protection.
Fan fault
The system has detected the
normal rotation of the fan.
Please ask the local authorized
technician for service.
Output Short
The effective maximum output
current of the three-phase is
more than 5 times of the rated
value within 100ms, namely
short circuit protection.
Confirm whether the connecting wire of
the load or the load itself is in normal
state and then press “FAULT CLEAR”
button for recovery.
EPO
Press the red button on the
panel or conduct the remote
EPO operation.
Remove the remote EPO order and
execute the
“OFF” operation steps
and
then execute the
“ON” steps after the
system power is cut OFF.
BAT disconnect
The breaker of the battery is
switched OFF.
Check whether the output air switch of
the battery or the battery itself is in
good condition.
Parallel
connection fault
The PE2 refers to single parallel
set
interface
(
“
1
—
parallel
operatio
n”
).
PF13 refers to the parallel
wires being connected well.
(
“
1
”
-OK for connection, one of
the following cases goes
wrong:
1.The connection of the parallel
wires for the single machine is
OK.
2.The connection of the parallel
wires for the parallel machines
fails.
Remarks: “exist”
refers that the fault arises and “clea
r
”
refers that the fault disappears.
Table 17 Comparison Table of Common Faults