Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
59
7.3.2 MPPT Troubleshooting:
Click
“
”
to switch the inverter and MPPT information for check.
Alarm Information
Explanation
Solutions
PV In Reverts
The polarity of PV input line of
the MPPT*# module is reversed.
Check and adjust polarity of
PV input line of the MPPT*#
module.
Module Fail
MPPT system fault
Please
ask
the
local
authorized technician for
service.
Comm Fail
MPPT
communication
is
interrupted.
Confirm whether screws of
MPPT module are loose.
Please
ask
the
local
authorized technician for
service.
Over Current
The power of PV polar plate is
too high and there is instant
overcurrent.
Check whether the power of
the polar pole confirms to
the system rated value.
Over-Temp
The power of the polar plate is
too
high
or
the
local
environment temperature rises
too
high
or
the
high-
temperature of the module is
caused by the fan fault.
•
Confirm whether the power
of the polar pole and the
environment temperature
exceed
the
system
requirements.
•
Please
ask
the
local
authorized technician for
service.
BUS Over Volt
The transient loading/unloading
causes the fluctuation of DC BUS.
•
The
system
automatic
adjustment recovers one
minute later.
•
If
the
overvoltage
phenomenon lasts for a long
time, please ask the local
authorized technician for
service.
PV In.C Over.V
The transient loading/unloading
causes the fluctuation of DC BUS.