completed. After the completion of the manual maintenance, the Energy Sever and the rectifier
are started normally, and the output is continuously switched to the AC inverter output and
recharges the battery. If necessary, the maintenance staff only needs to select the
“
CLR TEST
”
option in the
“
Test Order
”
menu to stop the battery manual maintenance, at this moment, the
Energy Sever will run in the normal working mode.
3.
Under the normal use condition, the service life of the battery is about 1~3 years. Under the
conditions of higher temperature, more frequent discharging and deeper depth of discharge, the
service life of the battery reduces to 0.5-1 year.
4.
With ageing of the battery, the performance of the battery gets poor. When the battery health
drops down to about 80% of the initial value, the discharge time decreases accordingly. The
battery should be tested every month instead of 3 months.
5.
Dustproof treatment:
•
Remove the dust and dirt on the battery.
•
Check whether all internal wires of the battery are connected firmly or broken, and when
necessary, it must be replaced and repaired.
•
Make sure that the batteries and battery terminals are tightened.
7.3 Troubleshooting:
•
Operation methods:
→
Click
“
”
for check.
7.3.1 Common Troubleshooting:
Alarm Information
Explanation
Solutions
AC fault
The phase sequence, voltage,
frequency or voltage unbalance
of the rectifier
’
s input power
supply goes wrong.
Check and make sure that the voltage
and the frequency of the input power
supply is according to the requirement
of the system equipment and whether
the switch is normal.
AC Volt Fail
The AC voltage exceeds the
system rated voltage.
Adjust the system input power or wait
for recovery (short fault).