PCR-LE2 series
PCR-LE2 Series models
The PCR-LE2 Series generates single-phase output. The following
models are available
Model
Rated output capacity
Maximum output current
Single-
phase,
Three-phse
Single-
phase
three-wire
Single-phase Single-phase
three-wire,
Three-phse
100 V
output
200 V
output
100 V
output
200 V
output
PCR6000LE2
6 kVA
4 kVA
60 A
30 A
20 A
10 A
PCR9000LE2
9 kVA
6 kVA
90 A
45 A
30 A
15 A
PCR12000LE2 12 kVA
8 kVA
120 A 60 A
40 A
20 A
PCR18000LE2 18 kVA
12 kVA
180 A 90 A
60 A
30 A
PCR27000LE2 27 kVA
18 kVA
270 A 135 A 90 A
45 A
This product consists of three power unit groups.
Model
Output capacity per group
PCR6000LE2
2 kVA
PCR9000LE2
3 kVA
PCR12000LE2
4 kVA
PCR18000LE2
6 kVA
PCR27000LE2
9 kVA
During single-phase output, all groups are used.
During single-phase three-wire output or three-phase output, each
phase (U, V and W) is assigned to a separate group.
During single-phase three-wire output, the phase W group is not
used. During three-phase output, all groups are used.
1group
power unit
Three-phase output
Single-phase three-wire output
1group
power unit
1group
power unit
1group
nonoperating
power unit
1group
power unit
1group
power unit
U
U
V
V
W
W
Precautions Concerning Installation
When installing this product, be sure to observe the precautions pro-
vided in “Precautions Concerning Installation Location” in the Safety
information manual. Items specific to this product are given below.
●
When you install the product, be sure to observe the temperature
and humidity ranges indicated below.
Operating temperature range: 0 °C to 50 °C (32 °F to 122 °F)
Operating humidity range: 20 %rh to 80 %rh (no condensation)
●
When you store the product, be sure to observe the temperature
and humidity ranges indicated below.
Storage temperature range: -10 °C to 60 °C (14 °F to 140 °F)
Storage humidity range: 90 %rh or less (no condensation)
●
Allow at least 20 cm of space between the air inlet/outlet and the
wall (or obstacles).
●
Fix PCR6000LE2s and PCR9000LE2s to the floor using L-shaped
or other similar brackets.
Base Hold Angles (OP03-KRC) are available as options.
Moving the product
Precautions when moving the PCR6000LE2/
PCR9000LE2
Note the following points when moving the product to the installa-
tion location or when transporting the product.
●
Raise the stopper.
Moving the product with the stopper lowered may cause injuries
due to the product falling over.
●
Unlock the casters.
●
Do not move the product by yourself.
Be sure to have two or more people move the product. Exercise
special care when carrying the product over a slope or across
steps.
Hold the product from underneath.
Check the product’s weight before you transport it. The weight is
displayed in the bottom of the rear panel.
If you are using a forklift, be sure to slide the forks under the bot-
tom of the product, check that the product is stable, and then
raise the product.
If you are using a band or similar item to raise the product with a
crane, be sure to slide the band under the bottom of the product,
check that the product is stable, and then raise the product.
●
When you move the product, do not tip the product on its side or
turn it upside down.
Locking the casters and using the stopper
This product has casters on its bottom side, so it is easy to move
the product. To ensure that the product is not moved accidentally
while it is being operated, use the stopper to fix the product in
place, and lock the casters.
Looking down at the stopper from above, turning the stopper to the
left (counterclockwise) raises the stopper, and turning the stopper
to the right (clockwise) lowers the stopper.
Lowering the lock lever on a caster locks the caster, and raising the
lock lever unlocks the caster.
Free
Lock
Down
Up
Stopper
Precautions when moving the PCR12000LE2/
PCR18000LE2/ PCR27000LE2
The PCR12000LE2/ PCR18000LE2/ PCR27000LE2 cannot be
moved after it has been installed. If you need to move it, contact
your Kikusui agent or distributor.