July 2016
-11-
K-76-1000
Figure 2 below shows that the square areas of coverage, A, B, and C, are all within the detector's circle of
coverage.
Figure 2. Heat Detector’s Circle of Coverage
Since all of the area within the detector’s circle of coverage is suitable for detecting a fire, the shape and
dimensions of the detector coverage “square” in Figure 3 may be modified. Note that, although the
coverage “square” is now a “rectangle,” the coverage area remains within the overall detector circle of
coverage.
Figure 3. Heat Detector Spacing, Rectangular Areas
1. Based on 50 ft. listed
spacing
Note: Smoke detectors are not listed for spacing
A
B
C
25 ft. x 34 ft. = 850
ft.² (7.6 m x 10.4 m = 79 m²)
20 ft. x 37 ft. = 740
ft.² (6.1 m x 11.3 m = 69 m²)
15 ft. x 39 ft. = 585
ft.² (4.6 m x 11.9 m = 54 m²)
10 ft. x 41 ft. = 410
ft.
² (3.1 m x 12.5 m = 38 m²)
30 ft. x 30 ft. = 900 ft.² (9.1 m x 9.1 m = 84 m²)
1
Summary of Contents for DS Series
Page 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Page 2: ......
Page 3: ...July 2016 1 K 76 1000 FOREWORD ...
Page 6: ...K 76 1000 4 July 2016 NOTES ...
Page 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Page 10: ...K 76 1000 8 July 2016 NOTES ...
Page 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Page 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Page 26: ...K 76 1000 24 July 2016 NOTES ...
Page 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Page 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Page 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Page 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Page 40: ...K 76 1000 38 July 2016 NOTES ...
Page 41: ......