SMOKE DETECTOR SPACING
The DS-PS spot-type smoke detector spacing recommendation of 30 ft. (9.1 m) ±5% or 18 in. (460 mm)
is based upon the detector installation on a smooth ceiling that is 10 ft. (3 m) high. Detector coverage is
typically represented as a square, because most structures have flat sidewalls. Like spot-type heat
detectors, smoke detector coverage is a circle whose radius is 0.7 times the listed spacing. Since all of
the area within the detector’s circle of coverage is suitable for detecting smoke from fire, the shape and
dimensions of the detector coverage “square” may be modified. Note that, although the coverage “square”
is a “rectangle,” the coverage area is within the overall detector circle coverage. (Refer to Figure 3.)
Note:
Unlike heat detectors, smoke detectors are not given a listed spacing. It is recommended that
smoke detectors be installed on S = 30 ft. (9.1 m) ±5% or 18 in. (460 mm) installed on “x” centers,
on smooth ceilings. NFPA 72, National Fire Alarm and Signaling Code contains additional infor-
mation regarding spacing adjustments.
Ceilings and Walls
Locate smoke detectors on the ceiling or, if on a sidewall, between the ceiling and 12 in. (300 mm) down
from the ceiling to the top of the detector.
Figure 10. DS-PS Smoke Detector Placement Near Ceiling/Wall Joints
For a smooth ceiling, for every point on the ceiling, locate the detector within a horizontal measurement
no greater than 0.7 times the selected spacing.
1. Smooth ceiling
2. Top of detector is acceptable in this area
3. Wall
4. Floor
2
3
4
12 in. (300 mm) max.
1
Summary of Contents for DS Series
Page 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Page 2: ......
Page 3: ...July 2016 1 K 76 1000 FOREWORD ...
Page 6: ...K 76 1000 4 July 2016 NOTES ...
Page 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Page 10: ...K 76 1000 8 July 2016 NOTES ...
Page 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Page 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Page 26: ...K 76 1000 24 July 2016 NOTES ...
Page 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Page 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Page 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Page 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Page 40: ...K 76 1000 38 July 2016 NOTES ...
Page 41: ......