July 2016
-21-
K-76-1000
Sloping Peaked-Typed Ceilings
In rooms with sloping peaked-type ceilings, place the first row of detectors within 3 ft. (1 m) (horizontally)
of the ceiling peak. Space additional detectors, if required, based upon the horizontal projection of the
ceiling and ceiling construction. This modification of spacing for smoke detectors on sloped ceilings is
identical to that used for spot-type heat detectors. Refer to Figure 5.
In rooms with sloping shed-typed ceilings having a slope:
•
Less than a 1 ft. in 8 ft. (1 m in 8 m) rise, treat as a level ceiling.
•
Greater than a 1 ft. in 8 ft. (1 m in 8 m) rise, place the first row of detectors within 36 in. (910 mm) of
the high end of the ceiling. Space additional detectors, if required, based upon the horizontal projec-
tion of the ceiling and ceiling construction.
•
Less than 30 degrees, adjust the horizontal spacing according to the height of the peak.
•
Greater than or equal to 30 degrees, adjust the horizontal spacing according to the average sloped
ceiling height.
This spacing modification for smoke detectors on sloped ceilings is identical to that used for spot-type heat
detectors. Refer to Figure 6.
Under-Floor Installation
When spot-type smoke detectors are installed under raised floors, they are subjected to high air velocities
and dust levels. Install the detectors with the base up or the base vertical (never down) as shown in Figure
13 below. This minimizes the effects of dirt, dust, and mechanical interference from cabling.
Figure 13. Permissible Smoke Detector Placement Under Raised Floors
A. Junction box secured to
structure
B. Junction box secured to floor
support
C. Junction box secured to angle
iron or channel support
1. Raised floor panel
2. Smoke detector
3. Junction box
4. Steel angle or channel
support
5. EMT or FMC conduit
6. Clamp
1
2
2
2
3
3
4
5
5
5
5
6
A
C
Summary of Contents for DS Series
Page 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Page 2: ......
Page 3: ...July 2016 1 K 76 1000 FOREWORD ...
Page 6: ...K 76 1000 4 July 2016 NOTES ...
Page 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Page 10: ...K 76 1000 8 July 2016 NOTES ...
Page 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Page 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Page 26: ...K 76 1000 24 July 2016 NOTES ...
Page 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Page 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Page 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Page 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Page 40: ...K 76 1000 38 July 2016 NOTES ...
Page 41: ......