K-76-1000
-14-
July 2016
Sloping Shed-Typed Ceilings
In rooms with sloped ceilings having a slope greater than 1 ft. in 8 ft. (1 m in 8 m), place the first row of
detectors within 36 in. (910 mm) of the high end of the ceiling, but not closer than 4 in. (100 mm) from the
adjoining wall or ceiling. (Refer to Figure 6 below.) Space additional detectors, if required, based upon the
horizontal projection of the ceiling and ceiling construction.
If the slope is:
•
Less than 7.2° (1 in 8), treat the ceiling as a level ceiling
•
Less than 30°, adjust the horizontal spacing according to the height of the peak
Greater than 30°, adjust the horizontal spacing according to the average sloped ceiling height or to the
height of the peak. This spacing modification for sloped shed-typed ceilings is identical for spot-type heat
detectors and smoke detectors.
Figure 6. Heat or Smoke Detector Spacing for Sloping Shed-Typed Ceilings
1. Heat or smoke detector
2. Do not mount detector in this area
3. Mount detector anywhere in this area
S = Listed spacing between DS-HFS detectors
= 50 ft. (15.2 m)
Summary of Contents for DS Series
Page 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Page 2: ......
Page 3: ...July 2016 1 K 76 1000 FOREWORD ...
Page 6: ...K 76 1000 4 July 2016 NOTES ...
Page 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Page 10: ...K 76 1000 8 July 2016 NOTES ...
Page 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Page 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Page 26: ...K 76 1000 24 July 2016 NOTES ...
Page 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Page 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Page 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Page 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Page 40: ...K 76 1000 38 July 2016 NOTES ...
Page 41: ......