K-76-1000
-12-
July 2016
When installed on the ceiling, locate the heat detectors a minimum of 4 in. (100 mm) from the wall. When
installed on walls, locate the detector between 4 in. (100 mm) and 12 in. (300 mm) from the ceiling, as
shown in Figure 4.
Figure 4. Heat Detector Placement Near Ceiling/Wall Joints
1. Smooth ceiling, place detector 4 in. (100 mm) from wall
2. Never in this area: 4 in. (100 mm) from top of wall or corner
3. Top of detector is acceptable in shaded area: 4 to 12 in. (100 to 300 mm)
from ceiling
4. Wall
5. Floor
2
3
4
5
4 in. (0.1 m) min.
12 in. (0.3 m) max.
4 in. (0.1 m) min.
4 in.
1
Summary of Contents for DS Series
Page 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Page 2: ......
Page 3: ...July 2016 1 K 76 1000 FOREWORD ...
Page 6: ...K 76 1000 4 July 2016 NOTES ...
Page 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Page 10: ...K 76 1000 8 July 2016 NOTES ...
Page 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Page 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Page 26: ...K 76 1000 24 July 2016 NOTES ...
Page 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Page 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Page 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Page 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Page 40: ...K 76 1000 38 July 2016 NOTES ...
Page 41: ......