
Troubleshooting
February 2012
7-8
P/N 06-237058-001
L#: Addr
9V DC FAULT On
Device
Type
A failure of the internally generated
9-Volt power supply for the SmartOne
smoke or heat detector at address
L#: Addr.
• Check SLC wiring. Refer to
Ensure
that wiring resistance and
capacitance limitations have not been
exceeded.
• Visually inspect the detector to
ensure that its red LED is flashing.
Use Handheld Programmer to test the
device if the LED is not flashing.
Replace the detector if it fails the
Handheld-Programmer test.
• List the automatic initiating device's
9-Volt level. Refer to the list menu in
Figure 3-16. Replace the device if the
9-Volt level varies by + / - 1.0
(nom.)
Vdc volts.
• Conduct an initiating device test on
the automatic detector. See
Section 3-3.4
• Activate and confirm a proper alarm
response from the detector.
• Replace the device if any of the above
tests are unsuccessful.
L#: Addr
ABORT TROUBLE On
Monitor Module
The abort switch being monitored by
the AI at address
L#: Addr
is activated
and the system is not in alarm
• Check abort switch for mechanical
failure
L#: Addr
ALARM TEST FAIL
Device
Type
An initiating device (i.e., automatic
detector or monitor module) at address
L#: Addr
failed a device test. The
initiating device was unable to send an
acceptable alarm-test signal when
requested by the control unit.
• Globally isolate all outputs. See the
Global Isolate menu in Figure 3-12.
• Disconnect device from SLC and
visually inspect for damage. Clean if
automatic detector.
• Use Handheld Programmer to test the
device. Reconnect device to SLC.
• Conduct an initiating device test on
the initiating device. Repeat this
procedure at least 3 times. Refer to
the Test SLC menu in Figure 3-37.
Check SLC wiring if test results are
inconsistent. Refer to Section 2-8.5.
Ensure that wiring-resistance and -
capacitance limitations have not been
exceeded.
• Activate and confirm a proper alarm
response from the initiating device
• Replace device if any of above tests is
unsuccessful.
• Globally de-isolate all outputs. See
Table 7-2. SLC Events (Continued)
SLC Events
For the following SLC-related events,
L#
is the SLC loop number and
Addr
is the
device address.
Error Message
Probable Cause
Corrective Action
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......