Networking
February 2012
5-10
P/N 06-237058-001
5-8.3
Operating States
A network of ARIES NET
Link
Systems has the five distinct Off-Normal operating states discussed in
Section 4-2. The normal network message display when there are no active system events is as
follows:
Figure 5-6. Network Normal Message Display
5-8.3.1
OPERATOR-DRIVEN MENU STATE
The system enters the Menu State when an operator presses the 0 Key and enters the appropriate
password as described in Section 4-8. The operator will be prompted to enter a network node
number. The requested menu will be accessible if the node number corresponds to:
•
The control unit whose display is being utilized
•
Another control unit in the same group as the control unit whose display is being
utilized
•
Any control unit in a network configured for global operation
•
The control unit whose display is being utilized is defined as Group 0
5-8.3.2
EVENT-DRIVEN STATES
A networked control unit will enter one of the event-driven states (pre-alarm, alarm, supervisory, or trouble)
when it is configured as Group 0 or when the event that occurs is:
•
Resident in the control unit or its associated peripheral devices
•
From another control unit in the same group as the control unit
•
From any control unit in a network configured for global operation
•
From a control unit in group 0 if Process Group 0 Events is configured
5-8.3.3
NETWORK OUTPUTS ACTIVATION
Control unit or SLC outputs can be activated via execution of operating instructions contained in each
networked control unit’s event output control (EOC) program. The EOC program for a particular
control unit is triggered by any event that transitions it from the Normal Mode to any of the Off-
Normal operating states discussed in Section 4-10. The control unit must be configured to selectively
receive and respond to the event as described Section 5-8.2
or the network must be configured for
global operation.
NORMA
L
N:0
1
CH
1
CH2 02:
1
5 PM
07/02/0
4
NORTH COMMUNICATIONS CENTER
System Normal
Message
Site-Specific
Custom Message
Node (Control Unit) Number
Dual-Channel System
Summary of Contents for ARIES NETLink
Page 2: ......
Page 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 293: ......